105,313Records 71,083Employers 85,290Hospitalizations 27,770Amputations 2015-01-01 2025-10-31
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #14243927

E GI II,ELECTRICAL,ELECTRICIAN,ELECTROCUTED,PANELBOARD,ELECTRICAL WORK,LOCKOUT,ELEC CIRC PART--MISC

Event
E GI II,ELECTRICAL,ELECTRICIAN,ELECTROCUTED,PANELBOARD,ELECTRICAL WORK,LOCKOUT,ELEC CIRC PART--MISC
Linked inspection
No inspection record linked to this accident's victims.
Summary number
14243927
Report ID
336000

Event description

ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Investigation abstract

AN EMPLOYEE WAS TESTING ENERGIZED ELECTRIC CIRCUITS IN AN ELECTRICAL CABINET. TH ELECTROCUTED. E EMPLOYEE WAS NOT USING ELECTRICAL PROTECTIVE EQUIPMENT AS THE USE OF PROTECTIV E EQUIPMENT WAS NOT REQUIRED BY HIS EMPLOYER. OF SIX CIRCUITS TO BE INSPECTED, F IVE HAD BEEN COMPLETED, AND THE LAST WAS BEING TESTED. THE FIVE PREVIOUSLY TESTE D CIRCUITS WERE TURNED "OFF". HOWEVER, BECAUSE OF A WIRING ERROR, THE FIFTH CIRC UIT WAS ENERGIZED WHILE THE SIXTH CIRCUIT WAS ENERGIZED. THE EMPLOYEE ASSUMED TH AT THE FIFTH CIRCUIT WAS DEENERGIZED, BUT HE HAD ONLY TESTED THE FIRST TWO OF TH E DEENERGIZED CIRCUITS TO ENSURE THAT THEY WERE IN FACT DEENERGIZED. WHILE HE WA S TESTING THE LAST CIRCUIT, HE ACCIDENTALLY CONTACTED THE FIFTH CIRCUIT AND WAS

Victim

  1. #1 Fatality Age 24 M

    Nature of injury
    10
    Part of body
    4
    Event type
    13
    Source
    15
    Occupation code
    999
    Human factor
    20
    Environmental factor
    13
    Task assigned
    1