Event description
ELECTRIC SHOCK - GROUND FAULT IN TRANSFORMER
Investigation abstract
A 240-VOLT TRANSFORMER WAS GROUNDED BY A CONDUIT CONTAINING THE FEEDER FROM A 48 0-VOLT ELECTRICAL SUPPLY CABINET. AN EMPLOYEE WAS LYING ON TOP OF THE TRANSFORME R ENCLOSURE TO REACH BETWEEN THE TRANSFORMER AND THE SUPPLY CABINET TO PICK UP A PIECE OF SCRAP PLASTIC CONDUIT. THE FEEDER CONDUIT PULLED FREE OF THE TRANSFORM ER ENCLOSURE, DISCONNECTING THE EQUIPMENT GROUNDING CONDUCTOR. AN APPARENT GROUN D FAULT IN THE TRANSFORMER CAUSED THE ELECTROCUTION OF THE EMPLOYEE.