OSHA Accident Investigation · Summary #14401871
ELEC PROTECT EQUIP,OVERHEAD POWER LINE,ELECTRICAL,POWER LINE WORKER,ELECTROCUTED,E PTD,ELEC UTILITY WORK,AERIAL LIFT
Event description
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE
Investigation abstract
THE CUTOUTS ON A TRANSFORMER HAD TO BE OPENED UNDER LOAD CONDITIONS DUE TO A FIR E IN A PLANT SERVED BY THE ELECTRIC POWER LINE. WHEN THE CUTOUTS WERE OPENED, A POWER SURGE RESULTED, WHICH CAUSED ONE OF THE CONDUCTORS OF THE 7200-VOLT OVERHE AD POWER LINE TO BURN IN TWO. THIS CONDUCTOR BECAME ENTANGLED WITH ONE OF THE OT HER CONDUCTORS. A POWER LINE WORKER WENT UP IN AN INSULATED AERIAL LIFT TO UNTAN GLE THE CONDUCTORS. HE WAS NOT WEARING RUBBER INSULATING GLOVES. HE WAS ELECTROC UTED WHEN GRABBED BOTH CONDUCTORS.
Victim
-
#1 Fatality Age 30 M
- Nature of injury
- 10
- Part of body
- 4
- Event type
- 13
- Source
- 15
- Occupation code
- 577
- Human factor
- 1
- Environmental factor
- 8
- Task assigned
- 1
Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.