105,313Records 71,083Employers 85,290Hospitalizations 27,770Amputations 2015-01-01 2025-10-31
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #14515035

ELEC PROTECT EQUIP,OVERHEAD POWER LINE,ELECTRICAL,POWER LINE WORKER,ELECTROCUTED,E PTD,ELEC UTILITY WORK,AERIAL LIFT

Event
ELEC PROTECT EQUIP,OVERHEAD POWER LINE,ELECTRICAL,POWER LINE WORKER,ELECTROCUTED,E PTD,ELEC UTILITY WORK,AERIAL LIFT
Linked inspection
No inspection record linked to this accident's victims.
Summary number
14515035
Report ID
524700

Event description

ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

Investigation abstract

AN EMPLOYEE WAS INSTALLING A TRANSFORMER ON A NEW 40-FOOT, CLASS 3 UTILITY POLE. OR BOTH HANDS ON THE JIB WHEN HE CONTACTED THE POWER LINE AT A POINT NEAR THE D EAD-END CLAMP. THE EMPLOYEE WAS ELECTROCUTED. THE 7200-VOLT PRIMARY OVERHEAD POWER LINE ON THE POLE WAS ENERGIZED. THE TRANSF ORMER WAS LOCATED ABOUT 8 INCHES BELOW AN EYEBOLT THAT SUPPORTS THE POWER LINE C ONDUCTOR. THE EMPLOYEE WAS WORKING FROM A TWO-PERSON BUCKET OF AN ALTEC AERIAL L IFT WITH A 50-FOOT REACH. ALTHOUGH INSULATING EQUIPMENT WAS AVAILABLE, THE POWER LINE WAS NOT COVERED WITH INSULATING EQUIPMENT, NOR WAS THE EMPLOYEE WEARING RU BBER INSULATING GLOVES OR SLEEVES. THE EMPLOYEE WAS EITHER INSTALLING A JIB ON T HE POLE OR ADJUSTING IT, WHEN HE CONTACTED THE OVERHEAD LINE WITH HIS LEFT SHOUL DER. FROM THE BURN MARKS ON THE EQUIPMENT, IT APPEARED THAT THE EMPLOYEE HAD ONE

Victim

  1. #1 Fatality Age 31 M

    Nature of injury
    10
    Part of body
    12
    Event type
    13
    Source
    15
    Occupation code
    577
    Human factor
    1
    Environmental factor
    18
    Task assigned
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.