OSHA Accident Investigation · Summary #903559
ELEC PROTECT EQUIP,OVERHEAD POWER LINE,ELECTRICAL,POWER LINE WORKER,ELECTROCUTED,E PTD,ELEC UTILITY WORK,ELECTRIC CONDUCTOR
Event description
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU JUMPER
Investigation abstract
A JOURNEYMAN POWER LINE WORKER HAD CLIMBED A 40-FOOT-HIGH UTILITY POLE TO CHANGE A 50-AMPERE CIRCUIT BREAKER ON THE CENTER PHASE OF A THREE-PHASE OVERHEAD POWER LINE. THE NEW CIRCUIT BREAKER HAD BEEN SECURED TO THE CROSSARM, AND THE LEFT JU MPER HAD BEEN CONNECTED INTO THE CIRCUIT BREAKER BUSHING. THE EMPLOYEE WAS CONNE CTING THE RIGHT JUMPER INTO THE CORRESPONDING BUSHING ON THE CIRCUIT BREAKER. TH E DANGLING JUMPER CONTACTED THE LEFT JUMPER, WHICH WAS ENERGIZED AT 7200 VOLTS. THE EMPLOYEE WAS ELECTROCUTED.
Victim
-
#1 Fatality Age 31 M
- Nature of injury
- 10
- Part of body
- 4
- Event type
- 13
- Source
- 15
- Occupation code
- 577
- Human factor
- 20
- Environmental factor
- 13
- Task assigned
- 1
Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.