CAPE CANAVERAL, FL —
OSHA Inspection: PRECISION MECHANICAL, INC.
Accident-driven inspection · Safety discipline
At a glance
On , OSHA opened an accident-driven safety inspection of PRECISION MECHANICAL, INC. in BEACH & PATROL ROADS CCAS,SLC-37B, CAPE CANAVERAL, FL 32920 (NAICS 000000). OSHA activity number 304706724.
Where did this inspection happen?
- Establishment
- PRECISION MECHANICAL, INC.
- Site address
- BEACH & PATROL ROADS CCAS,SLC-37B
- City
- CAPE CANAVERAL
- State
- FL
- ZIP
- 32920
- Mailing
- 505 CANAVERAL GROVES BLVD., COCOA, FL 32926
What kind of inspection was it?
- Inspection type
- Accident-driven (A)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- Yes
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 1711
- Employees
- 250
- Ownership type
- A
- Industry flags
- Construction safety.
Citations
3 citations on file for this inspection.
5(a)(1)
- Issued
- Abate by
- Penalty
- Initial $6300.00 · Current $3150.00 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the hazard of the sudden and unexpected, explosive release of nitrogen gas: A) Liquid Oxygen Pad, Space Launch Complex 37B, prior to the disassembly of temporary piping that had been used in the cleaning of the LOX system, the section of temporary piping to be disassembled was not vented (depressurized) to atmospheric pressure, on or about July 8, 2001. One feasible means of abatement, among others, would be to follow the safety procedures enunciated in The USAF Eastern and Western Range Safety Manual, 127-1, Section 6.11.5.1.4(a) and (b) 1. Depressurize the portion of the system to be worked upon prior to the initiation of disassembly; 2. Assure controlling valves are isolated from the source of gas pressure; 3. Apply lockout devices and warning tags to controlling valves to prevent unintended or unauthorized activation; 4. Establish and maintain a control area to assure that only personnel directly involved in the disassembly are in the area of the activity. ABATEMENT VERIFICATION REQUIRED:
Recent events (2)
- — F (S) $3150.00
- — Z (S) $6300.00
1926.102 A01
- Issued
- Abate by
- Penalty
- Initial $6300.00 · Current $6300.00
Recent events (2)
- — F (S) $6300.00
- — Z (S) $6300.00
1926.21 B02
- Issued
- Abate by
- Penalty
- Initial $63000.00 · Current $36850.00 Reduced
Recent events (2)
- — F (U) $36850.00
- — Z (W) $63000.00
More inspections at PRECISION MECHANICAL, INC.
USAF ACADEMY, CO—2024-10-09
PRECISION MECHANICAL, INC.
FT MYERS, FL—2004-03-04 00:00:00
PRECISION MECHANICAL INC.
CAPE CANAVERAL, FL—2001-07-09 00:00:00
PRECISION MECHANICAL, INC.
PHOENIX, AZ—1998-02-23 00:00:00
PRECISION MECHANICAL, INC.
TITUSVILLE, FL—1997-12-12 00:00:00
PRECISION MECHANICAL, INC.
View PRECISION MECHANICAL, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 000000)
SCHENECTADY, NY—2012-01-05 00:00:00
BRUCE D. BOWMAN
BILLINGS, MT—2005-01-25 00:00:00
KGC, INC.
ROCKAWAY, NJ—2002-12-31 00:00:00
ROCKAWAY BOROUGH DPW
FOREST CITY, NC—2002-12-31 00:00:00
HARRY BRICKEY DBA A. BRICKEY CEILING COMPANY
EDGERTON, KS—2002-12-31 00:00:00
SUDDEN BOND INDUSTRIES
More inspections in FL
MARIANNA, FL—2026-07-16
BRANNON BROTHERS CONSTRUCTION, LLC
LAKELAND, FL—2026-07-16
SOUTHERN MILLING & LUMBER, INC.
OAKLAND PARK, FL—2026-07-16
PKB CABINETRY
LAKELAND, FL—2026-07-16
ELIJAH WHOLESALE, LLC.
TAMPA, FL—2026-07-16
VALENCIA WHOLESALE, INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 304706724.