Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: MCLANE WESTERN

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of MCLANE WESTERN in 2100 E. HWY 119, LONGMONT, CO 80502 (NAICS 424410). OSHA activity number 304983000.

Watch Mclane Western — free Get an email when a new federal OSHA severe-injury report for Mclane Western is published. One employer, no account, unsubscribe in one click.
Establishment
MCLANE WESTERN
Site address
2100 E. HWY 119
City
LONGMONT
State
CO
ZIP
80502
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424410
SIC code (legacy)
5141
Employees
320
Ownership type
A

2 citations on file for this inspection.

5(a)(1)

Serious Gravity 03 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $1875.00 · Current $500.00 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish a place of employment which was free from recognized hazards that
were causing or
likely to cause death or serious physical harm to employees in that
employees were exposed
to caught in-between hazards:
(a)McLane Western at 2100 East Highway, Longmont, Co. 80502:  On or before
12/6/02, the employer did not provide adequate ventilation in the
mechanical room to
exhaust an accumulation of refrigerant due to leaks or rupture of the
ammonia system.
One feasible abatement method, among others, is to adhere to requirements
set forth
in ASHRAE standard 15-2001 Sections 8.11.4 - 8.11.5, which specifies
airflow
requirements in mechanical rooms where refrigerant is stored.
In addition, Section 8.11.2.1 of the ASHRAE standard provides that, unless
the fan is
operated continuously, the fan should be actuated by detector located in
the
mechanical room.  If the fan is operated continuously, Section 8.12(h)
provides that
an alarm is required upon failure of the mechanical ventilation system.
The
employer's fan operates continuously, but does not have an alarm that
actuates upon
failure.
Furthermore, Section 8.12(i) provides that ventilation fans shall be on a
separate
electrical circuit and have a control switch located immediately outside
the mechanical
room door.  The employer's ventilation control is located inside the
mechanical room.
Abatement Note:  Abatement certification is required for this item (See
enclosed "Sample
Abatement-Certification Letter").
Recent events (2)
  • — I (S) $500.00
  • — Z (S) $1875.00

1910.134 F01

Other-than-serious Gravity 01 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $1125.00 · Current $500.00 Reduced
Recent events (2)
  • — I (O) $500.00
  • — Z (S) $1125.00

View MCLANE WESTERN's full OSHA safety record →