Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: YONG SHING WHOLESALE

Accident-driven inspection · Safety discipline

On , OSHA opened an accident-driven safety inspection of YONG SHING WHOLESALE in 51 W. SOUTH WATER MARKET, CHICAGO, IL 60608 (NAICS 424490). OSHA activity number 305996399.

Watch Yong Shing Wholesale — free Get an email when a new federal OSHA severe-injury report for Yong Shing Wholesale is published. One employer, no account, unsubscribe in one click.
Site address
51 W. SOUTH WATER MARKET
City
CHICAGO
State
IL
ZIP
60608
Mailing
5115 S. MILLARD, CHICAGO, IL 60632
Inspection type
Accident-driven (A)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424490
SIC code (legacy)
5149
Employees
20
Ownership type
A

2 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $2100.00 · Current $2100.00
Section 5(a)(1) of the Occupational safety and Health Act of 1970:  The
employer
did not furnish
employment and a place of employment which were free from recognized
hazards that were
causing or likely to cause death or serious physical harm to employees in
that employees were
exposed to falling into the elevator shaft from a height of (13) feet:
First floor - On or about April 22, 2003 the freight elevator in the
facility at 51 West South
Water Market, Chicago, Il. 60608 was not provided with doors so
interlocked at each floor as
to prevent their opening when the freight elevator is not located at that
floor.
Among other methods one acceptable and feasible abatement method  to
correct this hazard is:
1. Conduct inspections of the elevator to assure that the doors and
interlocking devices are in
safe operating condition.
2. Follow the requirements of ANSI/ASME A17.3-1986 sec.2.7.1(b) which
requires that
hoistway doors for freight elevators shall be equipped with door
interlocks.  The interlocking
devices shall lock the door in a closed position before the elevator can
be operated. Also the
interlocking devices shall prevent the door from opening on any other
level than the specific
floor requested.

1910.23 B01 I

Serious Gravity 10 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $2100.00 · Current $2100.00

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 305996399.