Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: WINCHESTER COLD STORAGE CO., INC.

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of WINCHESTER COLD STORAGE CO., INC. in 605 N. LOUDOUN ST, WINCHESTER, VA 22601 (NAICS 493120). OSHA activity number 306816216.

Watch Winchester Cold Storage CO., INC. — free Get an email when a new federal OSHA severe-injury report for Winchester Cold Storage CO., INC. is published. One employer, no account, unsubscribe in one click.
Site address
605 N. LOUDOUN ST
City
WINCHESTER
State
VA
ZIP
22601
Mailing
P. O. BOX 45, WINCHESTER, VA 22601
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493120
SIC code (legacy)
4222
Employees
45
Ownership type
A
Industry flags
Manufacturing health.

5 citations on file for this inspection.

510001 A

Serious 5 instances 5 exposed
Issued
Abate by
Penalty
Initial $500.00 · Current $250.00 Reduced
Section 40.1-51.1(a) of the Code of Virginia:  The employer,  Winchester
Cold Storage Co. Inc., did not furnish
employment and a place of employment which was free from recognized
hazards that were causing or likely to cause
death or serious physical harm to employees in that employees were allowed
to ride freight elevators where they were
exposed to pinch points created when the elevator car passes a floor level.
In five freight elevators on site, the operator, freight handler, and
other passengers are exposed to  pinch points created
when the elevator car passes by the building floors and hoist-way openings
when the elevator ascends.  No door or gate
was provided to keep employees extremities from being caught in these
pinch points.
The American Society of Mechanical Engineers A17.1-1990, Safety Code for
Elevators and Escalators Rule 204.4a
Passenger and Freight Car Doors and Gates, General Requirements states: "A
door or gate shall be provided at each
car entrance."
One feasible method of abatement would be to install doors or gates on all
elevator car entrances.
Note: another feasible means of eliminating employee exposure would be to
relocate the operator control switch (dead man switch) to the middle
of the car wall.  The operator would be protected by distance from the
pinch points, since the car would stop if the operator released the
switch.
If this abatement method is used, the prohibition of passengers other than
the operator must be enforced.
Recent events (2)
  • — I (S) $250.00
  • — Z (S) $500.00

1910.23 C01

Serious 2 instances 5 exposed
Issued
Abate by
Penalty
Initial $375.00 · Current $200.00 Reduced
Recent events (2)
  • — I (S) $200.00
  • — Z (S) $375.00

1910.146 C04

Serious 1 instance 7 exposed
Issued
Abate by
Penalty
Initial $625.00 · Current $300.00 Reduced
Recent events (2)
  • — I (S) $300.00
  • — Z (S) $625.00

1910.134 C01

Other-than-serious 1 instance 5 exposed
Issued
Abate by

1910.147 C04 I

Other-than-serious 1 instance 5 exposed
Issued
Abate by

View WINCHESTER COLD STORAGE CO., INC.'s full OSHA safety record →