NEENAH, WI —
OSHA Inspection: FOX VALLEY ENERGY CENTER, LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of FOX VALLEY ENERGY CENTER, LLC in 231 MILLVIEW DR, NEENAH, WI 54956 (NAICS 562211). OSHA activity number 309840189.
Where did this inspection happen?
- Establishment
- FOX VALLEY ENERGY CENTER, LLC
- Site address
- 231 MILLVIEW DR
- City
- NEENAH
- State
- WI
- ZIP
- 54956
- Mailing
- 231 MILLVIEW DR., NEENAH, WI 54956
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 562211
- SIC code (legacy)
- 4953
- Employees
- 25
- Ownership type
- A
Citations
2 citations on file for this inspection.
5(a)(1)
- Issued
- Abate by
- Penalty
- Initial $1500.00 · Current $1050.00 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employmnent and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to severe burns and injuries from a dust fire: (a) On October 25, 2007, employees were exposed to a dust fire while clearing a jam in the cyclone collector. The drying system, including the cyclone system, was not properly operated, evaluated and analyzed to protect employees and to prevent fire hazards. Feasible means of abatement include, but are not limited to: Comply with National Fire Protection Association (NFPA) 654, 2006 edition: Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids; Chapter 4,"General Requirements". Conduct and implement a process hazard analysis of the facility, the process and the associated fire and explosive hazards. Special attention must be directed to section 4.6, of chapter 4; which outlines both prescriptive and performance-based methods of minimizing fire and explosion hazards for this type of process. Comply with National Fire Protection Association (NFPA) 654, 2006 edition: Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids, Chapter 5,"Performance-Based Design Options". Management must retain or use the services of a qualified dust explosion expert to determine if additional measures are necessary to be implemented, per this standard, to provide for safe processing and handling of the combustible paper pulp material. Of particular concern is an evaluation of the fire and explosion potential for the cyclone, the rotary dryers, and its associated duct work; and the installation of fire/explosion protection methods where necessary as prescribed in chapter 7. Abatement Certification and Abatement Documentation required.
Recent events (2)
- — I (S) $1050.00
- — Z (S) $1500.00
1910.22 A01
- Issued
- Abate by
- Penalty
- Initial $450.00 · Current $315.00 Reduced
Recent events (2)
- — I (S) $315.00
- — Z (S) $450.00
More inspections in this industry (NAICS 562211)
SIGNAL HILL, CA—2026-06-23
ARCWOOD ENVIRONMENTAL, LLC
FREMONT, CA—2026-05-19
VEOLIA NORTH AMERICA
CARTHAGE, MO—2026-03-31
ARCWOOD ENVIRONMENTAL-JOPLIN INC
AUBURN, KY—2026-03-26
68985 - APEX ENVIRONMENTAL LLC
EAST HARTFORD, CT—2026-03-26
TRADEBE ENVIRONMENTAL
More inspections in WI
WAUSAU, WI—2026-07-16
MIRON CONSTRUCTION CO. INC.
ELROY, WI—2026-07-15
WABASH NATIONAL SERVICES, L.P.
SUSSEX, WI—2026-07-15
KINGS SUPERIOR CONSTRUCTION LLC
DELAVAN, WI—2026-07-15
TERONOMY BUILDERS, INC.
DELAVAN, WI—2026-07-15
A. GOMEZ CARPENTRY, INC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 309840189.