EDISON, NJ —
OSHA Inspection: EQUISTAR CHEMICAL, LP
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of EQUISTAR CHEMICAL, LP in 340 MEADOW RD., EDISON, NJ 08817 (NAICS 331311). OSHA activity number 313979874.
Where did this inspection happen?
- Establishment
- EQUISTAR CHEMICAL, LP
- Site address
- 340 MEADOW RD.
- City
- EDISON
- State
- NJ
- ZIP
- 08817
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 331311
- SIC code (legacy)
- 2819
- Employees
- 65
- Ownership type
- A
- Industry flags
- Manufacturing safety.
Citations
6 citations on file for this inspection.
1910.119 E03 V
- Issued
- Abate by
- Penalty
- Initial $4500.00
General-duty citation text
29 CFR 1910.119(e)(3)(v): The process hazard analysis did not address facility siting: Equistar Chemicals Edison NJ Site - Facilty Wide a) The 2006 PHA did not address facility siting for the entire facility with respect to the Catalyst Production process and the effects of a catastrophic event on all neighboring buildings, vessels and structures. Condition noted on or about 5/28/2010 and 9/9/2010.
Recent events (3)
- — R (S)
- — J (S)
- — Z (S) $4500.00
1910.119 J02
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $3600.00 Reduced
General-duty citation text
29 CFR 1910.119(j)(2): The employer did not establish and implement written procedures to maintain the on-going mechanical integrity of process equipment: operating conditions existed before employees began the changeout procedure. Condition noted on or about 5/28/2010.
Recent events (3)
- — R (S) $3600.00
- — J (S) $3600.00
- — Z (S) $4500.00
1910.119 J05
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $3600.00 Reduced
General-duty citation text
29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that were outside acceptable limits (as defined by process information in 29 CFR 1910.119(d) before further use or in a safe and timely manner: Equistar Chemicals Edison NJ site - Building 6 a) C6-202: The pressure gauge PI-213 was not operational. Condition noted on or about 4/7/2010.
Recent events (3)
- — R (S) $3600.00
- — J (S) $3600.00
- — Z (S) $4500.00
1910.119 L01
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $3600.00 Reduced
General-duty citation text
29 CFR 1910.119(l)(1): The employer did not establish and implement written procedures to manage changes to process chemicals, technology, equipment, and procedures; and, changes to facilities that affect a covered process: Equistar Chemicals Edison NJ site - Building 6: a) A PMA (MOC) was not written for the change of PPE requirements in the "C202 Change Out" procedure. There was no evaluation performed to determine the possible hazards of changing from cotton uniforms to Pyrolon CRFR uniforms and from rubber gloves to nitrile gloves. Condition noted on or about 4/12/2010.
Recent events (3)
- — R (S) $3600.00
- — J (S) $3600.00
- — Z (S) $4500.00
1910.119 M06
- Issued
- Abate by
- Penalty
- Initial $4500.00 · Current $3600.00 Reduced
General-duty citation text
29 CFR 1910.119(m)(6): The incident investigation report was not reviewed with all affected personnel, including contract employees whose job tasks are relevant to the incident findings: Equistar Chemicals Edison NJ Site - Building 6 a) On 4/7/2010, maintenance employees performing a routine mole sieve change out the the C-202 column were exposed to a flash fire. An incident investigation was performed and completed on 5/10/2010 but was not reveiwed with all affected employees. Condition noted on or about 9/21/2010.
Recent events (3)
- — R (S) $3600.00
- — J (S) $3600.00
- — Z (S) $4500.00
1910.303 G01 II
- Issued
- Abate by
- Penalty
- Initial $1500.00 · Current $1200.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(ii): Working space about electric equipment rated 600 volts, nominal, or less was used for storage: Equistar Chemicals Edison NJ Site - a) Maintenance Shop/ Welding Area: Electrical panel boxes/ junction boxes rated 480V/3 phase and 220V single phase that controlled a welding machine, the exhaust fan and a lathe in the building were not maintained free of storage. The areas were blocked with items including but not limited to machinery, power cords and various other tools. Condition noted on or about 8/26/2010
Recent events (3)
- — R (S) $1200.00
- — J (S) $1200.00
- — Z (S) $1500.00
More inspections at EQUISTAR CHEMICAL, LP
CHANNELVIEW, TX—2013-10-22 00:00:00
EQUISTAR CHEMICAL, LP
CHANNELVIEW, TX—2006-08-14 00:00:00
EQUISTAR CHEMICAL, LP
CHANNELVIEW, TX—2001-10-01 00:00:00
EQUISTAR CHEMICAL, LP
CHANNELVIEW, TX—2000-03-21 00:00:00
EQUISTAR CHEMICAL, LP
CHANNELVIEW, TX—1998-04-15 00:00:00
EQUISTAR CHEMICAL, LP
View EQUISTAR CHEMICAL, LP's full OSHA safety record →
More inspections in this industry (NAICS 331311)
TUCSON, AZ—2013-05-01 00:00:00
SASOL NORTH AMERICA INC.
ANN ARBOR, MI—2013-03-19 00:00:00
PIDC
ANN ARBOR, MI—2013-03-19 00:00:00
PIDC
ANN ARBOR, MI—2013-03-19 00:00:00
PIDC
ANN ARBOR, MI—2013-02-26 00:00:00
PIDC
More inspections in NJ
PERTH AMBOY, NJ—2026-07-16
ENGLERT INC.
RIDGEFIELD, NJ—2026-07-16
COLORITE PLASTICS COMPANY
BERLIN, NJ—2026-07-16
URUS CONSTRUCTION CORPORATION
GLASSBORO, NJ—2026-07-15
GLASSBORO WATER & SEWER DEPARTMENT
FLANDERS, NJ—2026-07-15
TRI-STATE QUIKRETE
Source