OSHA Inspection: DATREX, INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DATREX, INC in 13878 HWY 165, KINDER, LA 70648 (NAICS 311999). OSHA activity number 334426343.

Watch Datrex, INC — free Get an email when a new federal OSHA severe-injury report for Datrex, INC is published. One employer, no account, unsubscribe in one click.
Establishment
DATREX, INC
Site address
13878 HWY 165
City
KINDER
State
LA
ZIP
70648
Mailing
13878 HWY 165, KINDER, LA 70648
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311999
Employees
36
Ownership type
A

2 citations on file for this inspection.

1910.305 G02 III

Serious Gravity 1 2 instances 1 exposed
Issued
Penalty
Initial $1785.00 · Current $1071.00 Reduced
29 CFR 1910.305(g)(2)(iii):     Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws.    a)	On or about May 22, 2012; in the Roto-Molder area of the jobsite, employees were allowed to utilize a port-a-cool (S/N-91927-05) fan which had an electrical plug that was not provided adequate strain relief.     b)	On or about May 22, 2012; in the Roto-Molder area of the jobsite, employees were allowed to utilize a portable cooler (S/N-C92) fan which had an electrical plug that was not provided adequate strain relief.
Recent events (2)
  • — I (S) $1071
  • — Z (S) $1785

1910.334 A03 I

Serious Gravity 1 1 instance 1 exposed
Issued
Penalty
Initial $1785.00 · Current $1071.00 Reduced
29 CFR 1910.334(a)(3)(i):     A flexible cord used with grounding type equipment shall contain an equipment grounding conductor.    a)	On or about May 22, 2012; in the Roto-Molder area of the jobsite, employees were allowed to utilize a port-a-cool (S/N-91927-05) fan which had an electrical plug with a ground pin that was plugged into a flexible extension cord which did not contain a grounding conductor.
Recent events (2)
  • — I (S) $1071
  • — Z (S) $1785