OSHA Inspection: MID-CONTINENT CABINETRY, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MID-CONTINENT CABINETRY, LLC in 900 S. MERIDIAN RD, NEWTON, KS 67114 (NAICS 337110). OSHA activity number 334653003.

Watch Mid-Continent Cabinetry, LLC — free Get an email when a new federal OSHA severe-injury report for Mid-Continent Cabinetry, LLC is published. One employer, no account, unsubscribe in one click.
Site address
900 S. MERIDIAN RD
City
NEWTON
State
KS
ZIP
67114
Mailing
900 S. MERIDIAN RD, NEWTON, KS 67114
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
337110
Employees
387
Ownership type
A

6 citations on file for this inspection.

1910.212 A01

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $3400.00 · Current $2380.00 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    At 900 S. Meridian Rd, Newton, KS in the maintenance building, the Enco Band saw was missing point of operation guarding on the left and right side of the 1" blade exposure, exposing employees to an amputation hazard.
Recent events (2)
  • — I (S) $2380
  • — Z (S) $3400

1910.303 B07 IV

Serious Gravity 5 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $3400.00 · Current $2380.00 Reduced
29 CFR 1910.303(b)(7)(iv): There were damaged parts that could adversely affect safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating.    At the building three entrance, an energized electrical receptacle has a broken, lower outlet with exposed electrical contacts, exposing employees to electrical shock.
Recent events (2)
  • — I (S) $2380
  • — Z (S) $3400

1910.303 B08 I

Serious Gravity 1 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(8)(i): Electric equipment was not firmly secured to the surface on which it was mounted    At the building three entrance, an energized electrical receptacle was not secured to the outlet box, exposing employees to electrical shock.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 A02 I

Serious Gravity 1 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2550.00 · Current $1785.00 Reduced
29 CFR 1910.305(a)(2)(i): Temporary electrical power and lighting installation(s) 600 volts, nominal, or less were used in prohibited manners:    At 900 S. Meridian Rd, Newton, KS, in Building 3 in the Edge Banding area, a seven-outlet power strip was plugged into a 25 feet extension cord.  The power strip was being used to power a box fan, exposing employees to a potential fire hazard.
Recent events (2)
  • — I (S) $1785
  • — Z (S) $2550

1910.333 A02

Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $3400.00 · Current $2380.00 Reduced
29 CFR 1910.333(a)(2): Where exposed live parts were not deenergized, other safety related work practices were not used to protect employees who could be exposed to the electrical hazards involved:    At 900 S. Meridian Rd, Newton, KS in the Edge Banding Area, the Holzma Panel Saw electrical control panel door latch was defective, leaving the door open, exposing employees to a shock hazard from the 460 VAC equipment contained inside the enclosure.
Recent events (2)
  • — I (S) $2380
  • — Z (S) $3400

1910.147 C04 II

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.147(c)(4)(ii): Procedures did not clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy, and the means to enforce compliance including, but not limited to, 29 CFR 1910.147(c)(4)(ii)(A), (c)(4)(ii)(B), (c)(4)(ii)(C) and (c)(4)(ii)(D)(h):    In Building 1, the Viet Wide Belt Sander Lockout/Tagout procedures were inadequate for the control of hazardous energy in that the procedures developed did not correctly identify the electrical disconnect on the front of the machine as the proper lockout/tagout location, nor did the procedures address the control of the pneumatic energy on the equipment.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334653003.