OSHA Inspection: DEPENDABLE BAGGING CO., INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DEPENDABLE BAGGING CO., INC. in 264 HORD ST., HARAHAN, LA 70123 (NAICS 327390). OSHA activity number 335225397.

Watch Dependable Bagging CO., INC. — free Get an email when a new federal OSHA severe-injury report for Dependable Bagging CO., INC. is published. One employer, no account, unsubscribe in one click.
Site address
264 HORD ST.
City
HARAHAN
State
LA
ZIP
70123
Mailing
264 HORD ST., HARAHAN, LA 70123
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327390
Employees
12
Ownership type
A

3 citations on file for this inspection.

1910.303 G01 I A

Serious Gravity 1 1 instance 1 exposed
Issued
Penalty
Initial $1200.00 · Current $720.00 Reduced
29 CFR 1910.303(g)(1)(i)(A):     For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910:    (a) The employer does not ensure that electrical equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts was not less than indicated in Table S-1 of Subart S of Part 1910.  This violation occurred on or about July 13, 2012 when the main power inlet panels in the warehouse had only sixteen (16) inches of clearance where three (3) feet were required as indicated in Table S-1 of Subpart S of Part 1910.
Recent events (2)
  • — I (S) $720
  • — Z (S) $1200

1910.305 G02 III

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $2000.00 · Current $1200.00 Reduced
29 CFR 1910.305(g)(2)(iii):     Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws.    a)  The employer does not ensure that flexible cords and cables are connected to fittings so that strain relief is provided that will prevent pull from being directly transmitted to the joint or terminal screws.  This violation occurred on or about July 13, 2012 in the liquid filling area when the power cable for the scale (Michellli Scales Model QC3265) was damaged from strain at the plug end of the cord.
Recent events (2)
  • — I (S) $1200
  • — Z (S) $2000

1910.304 G05

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.304(g)(5):     The path to ground from circuits, equipment, and enclosures was not permanent, continuous and effective:    (a)  The employer does not ensure that the path to ground from circuites, equipment, and enclosures is permanent, contiunous and effective.  This violation occurred on or about July 13, 2012 when a metal Michelli Scale (Model QC-3265) in the liquid filling area did not have a continuous path to ground.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

OXYCHEM