Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: KAHLUND ENTERPRISES, INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of KAHLUND ENTERPRISES, INC. in 3645 MT HIGHWAY 200 E, MISSOULA, MT 59802 (NAICS 238130). OSHA activity number 335322780.

Watch Kahlund Enterprises, INC. — free Get an email when a new federal OSHA severe-injury report for Kahlund Enterprises, INC. is published. One employer, no account, unsubscribe in one click.
Site address
3645 MT HIGHWAY 200 E
City
MISSOULA
State
MT
ZIP
59802
Mailing
3645 HWY 200 EAST, MISSOULA, MT 59802
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238130
Employees
9
Ownership type
A

12 citations on file for this inspection.

1910.22 A01

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $1000.00 Reduced
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms, and service rooms were not kept clean and orderly and in a sanitary condition:    (a) Air Compressor Room: On or about 18 July 2012 and at times prior thereto, employees were exposed to fire and explosion hazards from a buildup of approximately 1 inch of Class II dust on the wall bracing, duplex receptacle and near the open air compressor motor.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $2000

1910.134 C02

Serious Gravity 1 4 instances 3 exposed
Issued
Abate by
Penalty
Initial $1200.00 · Current $1000.00 Reduced
29 CFR 1910.134(c)(2):     The employer did not develop and implement a respiratory protection program in accordance with sections i and ii of this paragraph (c)(2) for employees who chose to wear respirators where respirator use was not required:    (a) Finish Shop: On or about 18 July 2012 and at times prior the Employer had not established a written respiratory program, had not verified that the employees were medically able to wear a 3M, model 6200, 1/2 face respirator, and did not ensure that the 3M, model 6200, 1/2 face respirators were properly cleaned, stored and maintained to prevent a health hazard to the user.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $1200

1910.212 A01

Serious Gravity 5 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $1600.00 · Current $800.00 Reduced
29 CFR 1910.212(a)(1):     One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    (a) Milling Shop: On or about 18 July 2012 and at times prior, employees were exposed to the hazard created by rotating parts when operating the JET Drill Press, model JDP-17MF, without a chuck guard.    (b) Framing Building: On or about 18 July 2012 and at times prior, employees were exposed to the hazard created by rotating parts when operating the Shopsmith drill press without a chuck guard.
Recent events (2)
  • — I (S) $800
  • — Z (S) $1600

1910.219 D01

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $1000.00 Reduced
29 CFR 1910.219(d)(1):     Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o):      (a) Compressor Room: On or about 18 July 2012 and at times prior, employees were exposed to unguarded pulleys when working with or around the Speedaire Air Compressor, in the air compressor room located in the Finish shop, subjecting them to an amputation hazard from rotating drum drive pulleys.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $2000

1910.219 E03 I

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.219(e)(3)(i):     Vertical or inclined belt(s) were not enclosed by guard(s) conforming to the requirements specified at 29 CFR 1910.219(m) and (o):      (a) Compressor Room: On or about 18 July 2012 and at times prior, employees were exposed to unguarded inclined belts when working with or around the Speedaire Air Compressor with the guard removed, subjecting them to an amputation hazard from rotating belts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.242 B

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $1000.00 Reduced
29 CFR 1910.242(b):     Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.:    (a) Milling Shop: On or about 18 July 2012 and at times prior, employees were exposed to the hazard of injecting air into their skin when using an air nozzle with air pressures greater than 100 p.s.i. to clean dust from equipment and themselves.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $2000

1910.304 F01 IV

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $1000.00 Reduced
29 CFR 1910.304(f)(1)(iv):     Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel:    (a) Finish Room: On or about 18 July 2012 and at times prior, employees are exposed to amputation hazards if equipment needed to be disconnected in the event of an emergency and/or locked and tagged out for maintenance for equipment such as but not limited to the Profile Grinder.     (b) Throughout the facility: On or about 18 July 2012 and at times prior, access to the transformer, equipment breakers and lighting panels were blocked by storage. Examples include but are not limited to: (a) in the framing building the lighting and breaker panels were blocked by storage boxes containing frame corner molding samples, (b) in the finish shop access inside the partitioned room containing the transformer and the panels containing equipment disconnects and lighting breakers was blocked by storage.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $2000

1910.304 G05

Other-than-serious 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $2400.00 · Current $0.00 Reduced
29 CFR 1910.304(g)(5): The paths to ground from circuits, equipment, and enclosures were not permanent, continuous, and effective:    (a) Finish Shop: On or about 18 July 2012 and at times prior employees were exposed to shock hazards due to a missing ground plug on the orange flexible cord to the dust collector.
Recent events (2)
  • — I (O) $0
  • — Z (S) $2400

1910.334 A02 II

Other-than-serious 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.334(a)(2)(ii):     There was a defect or evidence of damage that could have exposed an employee to injury and the defective or damaged item was not removed from service:    (a) Finish Shop: On or about 18 July 2012 and at times prior the Company had not removed form service damaged flexible cords, examples include but are not limited to a missing ground plug on the orange flexible cord to the dust collector.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 5 2 instances 3 exposed
Issued
Abate by
Penalty
Initial $1600.00 · Current $800.00 Reduced
29 CFR 1910.305(b)(1)(ii):     Unused openings in boxes, cabinets, or fittings were not effectively closed:      (a) Milling Shop: On or about 18 July 2012 and at times prior, the 2 phase 230 Volt electrical receptacle for the Embosser had an open conduit hole that was not being used nor plugged, thereby exposing employees to the hazard of a fire.     (b) Finish Shop: On or about 18 July 2012 and at times prior, there were two junction boxes on the west wall that did not have covers over the openings, thereby exposing employees to the hazard of a fire or shock.
Recent events (2)
  • — I (S) $800
  • — Z (S) $1600

1910.305 G01 IV B

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $620.00 Reduced
29 CFR 1910.305(g)(1)(iv)(B):     Flexible cords and cables were run through holes in walls, ceilings, or floors:    (a) Finish Shop: On or before 18 July 2012 and at times prior, flexible cords were run thorough walls at locations including but not limited to the south side of the Speedaire compressor room and also inside that same compressor room a flexible cord was knotted around the electrical conduit and then it passed through the north wall of the room. Employees were exposed to shock hazards from temporary wiring hidden behind a wall and it was not known if the cord had sustained damage.
Recent events (2)
  • — I (S) $620
  • — Z (S) $2000

1910.307 C

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $500.00 Reduced
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location:    (a) Compressor Room: On or about 18 July 2012 and at times prior thereto, employees were exposed to fire and explosion hazards from having a non-intrinsically safe outlet and light switch in the Compressor Room which contained a build-up of approximately 1 inch of Class II dust.
Recent events (2)
  • — I (S) $500
  • — Z (S) $2000

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 335322780.