FORT LEONARD WOOD, MO —
OSHA Inspection: E.D.P. ENTERPRISES, INC.
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of E.D.P. ENTERPRISES, INC. in BUILDING 2318, FORT LEONARD WOOD, MO 65473 (NAICS 722310). OSHA activity number 335727780.
Where did this inspection happen?
- Establishment
- E.D.P. ENTERPRISES, INC.
- Site address
- BUILDING 2318
- City
- FORT LEONARD WOOD
- State
- MO
- ZIP
- 65473
- Mailing
- P.O. BOX 349, FORT LEONARD WOOD, MO 65473
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 722310
- Employees
- 920
- Ownership type
- A
Citations
10 citations on file for this inspection.
1910.36 D01
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $7000.00
General-duty citation text
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: (a) On or about August 9, 2012 the emergency exit in building 630 was locked when employees were working. (b) Padlocks were used to lock emergency exits in four of the dining facilities.
Recent events (2)
- — I (S) $7000
- — Z (S) $7000
1910.37 A03
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: (a) Exit routes were blocked by storage racks and stacks of supplies.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.304 G05
- Issued
- Abate by
- Penalty
- Initial $4000.00 · Current $3000.00 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures were not permanent, continuous, and effective: (a) Fans were missing their ground pins; (b) Warming lights connected by cord and plug were not removed from service when the ground pin was missing and the cord was damaged.
Recent events (2)
- — I (O) $3000
- — Z (S) $4000
1910.305 B02
- Issued
- Abate by
- Penalty
- Initial $3000.00 · Current $2250.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(2): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: (a) A duplex outlet was missing a cover; (b) Duplex outlets had cracked and damaged covers;
Recent events (2)
- — I (O) $2250
- — Z (S) $3000
1910.305 E01
- Issued
- Penalty
- Initial $6000.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in wet locations were not weatherproof: (a) Duplex outlets located where water could splash on them did not have a protective cover.
Recent events (2)
- — I (S) $0
- — Z (S) $6000
1910.305 A02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(a)(2)(i): Temporary electrical power and lighting installation(s) 600 volts, nominal, or less were used in prohibited manners: (a) Temporary electrical power was used to provide energy to a freezer in lieu of permanent wiring; (b) Temporary electrical power was used to provide energy to a warming oven in lieu of permanent wiring.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 A02 IX
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(a)(2)(ix): Lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lampholder with a guard: (a) Lamps in freezers where condensation was present were not protected from accidental contact or breakage.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 A02 X
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(a)(2)(x): Flexible cords and cables were not protected from accidental damage: (a) At the serving lines electrical cords from equipment resting on stainless steel cabinets was run through openings in the metal cabinets and not protected from being cut by the sharp metal edges.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 J01 IV
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(j)(1)(iv): Fixtures installed in wet or damp locations were not approved for the purpose and were not so constructed or installed that water could not enter or accumulate in wireways, lampholders, or other electrical parts: (a) In the dish washing areas seal tight connection were not installed such that water could not accumulate in the wireways supplying electrical service to the hygienic wash units.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 J02 IV
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(j)(2)(iv): Receptacles installed in wet or damp locations were not suitable for the location: (a) Receptacles installed next to water cooler drinking fountains were not designed for wet locations; (b) Receptacles next to sinks and in the back splashes of sinks were not designed for wet locations.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 722310)
DUBLIN, CA—2026-06-24
ARAMARK SERVICES, INC.
SWANTON, VT—2026-06-12
WHITSONS RESOURCE MANAGEMENT LLC
HUMACAO, PR—2026-06-11
ENCANTO RESTAURANTS, INC
AUSTELL, GA—2026-06-10
CREATION GARDENS, INC.
KEAAU, HI—2026-05-05
COMPASS GROUP USA INC
More inspections in MO
CLINTON, MO—2026-07-14
TORCHYLO BUILDERS, LLC.
KANSAS CITY, MO—2026-07-09
NIAGARA BOTTLING
MONETT, MO—2026-07-09
MONETT METALS INC.
PARKVILLE, MO—2026-07-08
SKY-TECH ROOFING, LLC.
SPRINGFIELD, MO—2026-07-07
D & C CONSTRUCTION, LLC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 335727780.