Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: E.D.P. ENTERPRISES, INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of E.D.P. ENTERPRISES, INC. in BUILDING 2318, FORT LEONARD WOOD, MO 65473 (NAICS 722310). OSHA activity number 335727780.

Watch E.D.P. Enterprises, INC. — free Get an email when a new federal OSHA severe-injury report for E.D.P. Enterprises, INC. is published. One employer, no account, unsubscribe in one click.
Site address
BUILDING 2318
City
FORT LEONARD WOOD
State
MO
ZIP
65473
Mailing
P.O. BOX 349, FORT LEONARD WOOD, MO 65473
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
722310
Employees
920
Ownership type
A

10 citations on file for this inspection.

1910.36 D01

Serious Gravity 10 2 instances 200 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $7000.00
29 CFR 1910.36(d)(1):     Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge:    (a) On or about August 9, 2012 the emergency exit in building 630 was locked when employees were working.    (b) Padlocks were used to lock emergency exits in four of the dining facilities.
Recent events (2)
  • — I (S) $7000
  • — Z (S) $7000

1910.37 A03

Serious Gravity 10 1 instance 200 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(a)(3):     Exit route(s) were not kept free and unobstructed:    (a) Exit routes were blocked by storage racks and stacks of supplies.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.304 G05

Other-than-serious 2 instances 920 exposed
Issued
Abate by
Penalty
Initial $4000.00 · Current $3000.00 Reduced
29 CFR 1910.304(g)(5):   The path to ground from circuits, equipment, and enclosures were not permanent, continuous, and effective:    (a) Fans were missing their ground pins;    (b) Warming lights connected by cord and plug were not removed from service when the ground pin was missing and the cord was damaged.
Recent events (2)
  • — I (O) $3000
  • — Z (S) $4000

1910.305 B02

Other-than-serious 2 instances 50 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $2250.00 Reduced
29 CFR 1910.305(b)(2):     Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:         (a)  A duplex outlet was missing a cover;    (b)  Duplex outlets had cracked and damaged covers;
Recent events (2)
  • — I (O) $2250
  • — Z (S) $3000

1910.305 E01

Deleted Serious Gravity 5 1 instance 30 exposed
Issued
Penalty
Initial $6000.00 · Current $0.00 Reduced
29 CFR 1910.305(e)(1):     Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in wet locations were not weatherproof:       (a) Duplex outlets located where water could splash on them did not have a protective cover.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6000

1910.305 A02 I

Deleted Serious Gravity 5 3 instances 200 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(a)(2)(i):     Temporary electrical power and lighting installation(s) 600 volts, nominal, or less were used in prohibited manners:        (a) Temporary electrical power was used to provide energy to a freezer in lieu of permanent wiring;    (b) Temporary electrical power was used to provide energy to a warming oven in lieu of permanent wiring.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 A02 IX

Deleted Serious Gravity 5 1 instance 200 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(a)(2)(ix):     Lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lampholder with a guard:      (a) Lamps in freezers where condensation was present were not protected from accidental contact or breakage.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 A02 X

Deleted Serious Gravity 5 1 instance 920 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(a)(2)(x):     Flexible cords and cables were not protected from accidental damage:    (a) At the serving lines electrical cords from equipment resting on stainless steel cabinets was run through openings in the metal cabinets and not protected from being cut by the sharp metal edges.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 J01 IV

Deleted Serious Gravity 5 1 instance 200 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(j)(1)(iv):     Fixtures installed in wet or damp locations were not approved for the purpose and were not so constructed or installed that water could not enter or accumulate in wireways, lampholders, or other electrical parts:    (a) In the dish washing areas seal tight connection were not installed such that water could not accumulate in the wireways supplying electrical service to the hygienic wash units.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 J02 IV

Deleted Serious Gravity 5 2 instances 920 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(j)(2)(iv):     Receptacles installed in wet or damp locations were not suitable for the location:    (a) Receptacles installed next to water cooler drinking fountains were not designed for wet locations;    (b) Receptacles next to sinks and in the back splashes of sinks were not designed for wet locations.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 335727780.