OSHA Inspection: POWER CONTRACTING COMPANY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of POWER CONTRACTING COMPANY in 220 SCOTLAND ROAD, EDINBORO, PA 16444 (NAICS 238210). OSHA activity number 335939005.

Watch Power Contracting Company — free Get an email when a new federal OSHA severe-injury report for Power Contracting Company is published. One employer, no account, unsubscribe in one click.
Site address
220 SCOTLAND ROAD
City
EDINBORO
State
PA
ZIP
16444
Mailing
61 ARCH STREET, CARNEGIE, PA 15106
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
40
Ownership type
A

2 citations on file for this inspection.

1926.403 B02

Serious Gravity 5 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1480.00 Reduced
29 CFR 1926.403(b)(2):    Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:     a) Power Contracting Company / 220 Scotland Road, Edinboro, PA: On or about August 22, 2012 above the data center on the first floor, North section of existing building: A temporary knockout style receptacle outlet box was on the ground. The box was used in a portable application and not utilized in accordance with its listing in labeling in that it was not designed for a portable application and was to be surface mounted.     b) Power Contracting Company / 220 Scotland Road, Edinboro, PA: On or about August 22, 2012 above the data center on the first floor, North section of the existing building: There was Type NM cable laying on the ground and routed through a hole in the floor to the temporary knockout style receptacle outlet box. Type NM cable was exposed to physical damage in that it was not protected from damage where it came through the floor hole. Type NM cable was also exposed to physical damage from construction materials, foot traffic and equipment.
Recent events (2)
  • — I (S) $1480
  • — Z (S) $2800

1926.405 A02 II B

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.405(a)(2)(ii)(B):   Branch circuit conductors were laid on the floor:    a.) Power Contracting Company / 220 Scotland Road, Edinboro, PA:  On or about August 22, 2012 above the data center on the first floor, North section of the existing building: Type NM cable was routed across the floor. There was a Type NM cable laying on the ground and routed through a hole in the floor to the temporary knockout style receptacle outlet box. Type NM cable was exposed to physical damage in that it was not protected from damage where it came through the floor hole. Type NM cable was also exposed to physical damage from construction materials, foot traffic and equipment.