Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: DEPT OF VETERANS AFFAIRS-VETERANS HEALTH ADMIN.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of DEPT OF VETERANS AFFAIRS-VETERANS HEALTH ADMIN. in 601 HIGHWAY 6 WEST, IOWA CITY, IA 52246 (NAICS 622310). OSHA activity number 336004585.

Watch Dept OF Veterans Affairs-Veterans Health Admin. — free Get an email when a new federal OSHA severe-injury report for Dept OF Veterans Affairs-Veterans Health Admin. is published. One employer, no account, unsubscribe in one click.
Site address
601 HIGHWAY 6 WEST
City
IOWA CITY
State
IA
ZIP
52246
Mailing
601 HIGHWAY 6 WEST, IOWA CITY, IA 52246
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Case closed
Last modified
Data loaded
NAICS code
622310
Employees
1300
Ownership type
D

5 citations on file for this inspection.

1910.23 A08

Serious Gravity 5 2 instances 8 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.23(a)(8):     Every floor hole into which persons can accidentally walk were not guarded:    (a) BW02 Shaft Level 8 - The floor area ajacent to the access ladder was covered by grating except a hole measured 8 inches long by 9 inches wide with a fall or drop of >12 feet was not protected by the grating or guarded to protect employees from stepping into the hole.      (b) BW02 Shaft Level 8 - The grating adjacent to the mechanical ducting left a gap that measured 63 inches long and 7 inches wide with a drop of >12 feet.  This unprotected floor was not guarded to protect employees from stepping into the opening.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.23 C01

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.23(c)(1): Open-sided platform(s) 4 feet or more above the adjacent floor or ground level were not guarded by standard railings (or the equivalent as specified in 29 CFR 1910.23(e)(3)(i) through (v)), on all open sides:    (a) East Shaft - Maintenance employees accessed a platform in the east shaft to perform maintenance activity via a 32 inch x 32 inch doorway from the hallway. This platform had no standard railings or equivalent fall protection exposing employees to a fall hazard of 15-20 feet.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.23 E01

Serious Gravity 5 3 instances 15 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.23(e)(1): Standard railing(s) did not consist of top rail, intermediate rail and/or posts and/or did not have a vertical height of 42 inches (106.7 cm) nominal from upper surface of top rail to floor, platform runway, or ramp level:    (a) BW02 Shaft Level 3 - The rails around the floor opening for the access ladder was missing the intermediate or mid-rail.   Employees were exposed to a fall of approximately 10-12 feet to the lower level.    (b) BW02 Shaft Level 5 - The rails around the floor opening for the access ladder was missing the intermediate or mid-rail.  Employees were exposed to a fall of approximately 10-12 feet to the lower level.    (c) BW02 Shaft Level 8 - The rails around the floor opening for the access ladder was missing the intermediate or mid-rail.  When measured, the top rail was 35 inches in height and the width of the opening was 28 inches. Employees were exposed to a fall of approximately 10-12 feet to the lower level.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.1101 K06

Serious Gravity 5 1 instance 15 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00

Hazardous substances 9020

29 CFR 1926.1101(k)(6): At the entrance of the mechanical rooms/areas in which employees could reasonably be expected to enter and which contained ACM and/or PACM, the building owner did not post signs identifying the material present, its location, and appropriate work practice which, if followed will ensure that asbestos containing material and/or presumed asbestos containing material will not be disturbed:    (a)  BW02 Shaft - Although signs were posted at the access doors identifying that ACM was present in the shaft, there were no signs regarding appropriate work practices to ensure that ACM material would not be disturbed.  On the 3rd level of the shaft, recent electrical work by an outside contractor had been conducted and a conduit pipe had been place against the ACM pipe insulation potentially damaging the insulation.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.1101 K09 VI

Serious Gravity 5 1 instance 15 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.1101(k)(9)(vi): Training for employees performing Class IV operations did not include available information concerning the locations of thermal system insulation and surfacing asbestos containing material and/or presumed asbestos containing material, asbestos-containing flooring materials, or flooring material where the absence of asbestos has not yet been certified; and instruction in recognition of damage, deterioration, and delamination of asbestos containing building materials; and did not take at least 2 hours:    (a) BW02 Shaft - In the course of conducting maintenance activities, including but not limited to, installation of lighting, painting insulated materials, running electrical wiring, or repairing leaking water lines, maintenance employees were not provided training that included the specific locations of the ACM thermal system insulation and sufacing materials, how to recognize damaged or deteriorated ACM and/or the proper response to all fiber release episodes when these employees entered and conducted work in the shaft.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View DEPT OF VETERANS AFFAIRS-VETERANS HEALTH ADMIN.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336004585.