MANVEL, TX —
OSHA Inspection: SOUTHWEST QUALITY MOLDING
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of SOUTHWEST QUALITY MOLDING in 7900 BISSELL RD, MANVEL, TX 77578 (NAICS 326199). OSHA activity number 336926183.
Where did this inspection happen?
- Establishment
- SOUTHWEST QUALITY MOLDING
- Site address
- 7900 BISSELL RD
- City
- MANVEL
- State
- TX
- ZIP
- 77578
- Mailing
- 7900 BISSELL RD, MANVEL, TX 77578
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326199
- Employees
- 25
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.215 A04
- Issued
- Abate by
- Penalty
- Initial $1200.00 · Current $1200.00
General-duty citation text
29 CFR 1910.215(a)(4): Grinding machinery was not used with work rest(s) to support offhand grinding work: a) On or about October 17, 2012, at the facility, the Dayton bench grinder, serial number 2Z341N, lacked a work rest, causing struck-by and caught-in hazards.
Recent events (1)
- — Z (S) $1200
1910.215 B09
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch: a) On or about October 17, 2012, at the facility, the safety guard peripheral member on the Dayton bench grinder, serial number 2Z341N, was 0.75 inches from the abrasive wheel, causing struck-by and caught-in hazards.
Recent events (1)
- — Z (S) $0
1910.303 G02 I
- Issued
- Abate by
- Penalty
- Initial $2800.00 · Current $2800.00
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) On or about October 17, 2012 at the facility the bench drill was powered by a flexible cord that had the wiring exposed. This condition exposes the employees to electrical hazards.
Recent events (1)
- — Z (S) $2800
1910.305 G01 IV A
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) On or about October 17, 2012, at the facility, a bench drill was powered by a flexible cord instead of permanent wiring, exposing employees to electrical hazards.
Recent events (1)
- — Z (S) $0
1910.305 G02 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: a) On or about October 17, 2012, at the facility, a flexible cord used to power the bench drill, lacked strain relief exposing employees to electrical hazards.
Recent events (1)
- — Z (S) $0
1910.147 C01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.147(c)(1): The employer did not establish an energy control program consisting of energy control procedures, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, start up or release of stored energy could occurr and cause injury, the machine or equipment would be isolated, and rendered inoperative: a) On or about October 17, 2012, at the facility, an energy control program had not been established. Maintenance is performed on equipment such as, but not limited to, the Van Dorn 300 molding machine.
Recent events (1)
- — Z (O) $0
1910.157 E03
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check: a) On or about October 17, 2012, at the facility, the portable fire extinguishers had not been inspected annually. Fire extinguishers had their tags showing that they were due in September 2012.
Recent events (1)
- — Z (O) $0
1910.178 L04 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.178(l)(4)(i): The powered industrial truck operators (PITs) were not trained and evaluted once in three years: a) On or about October 17, 2012, at the facility, employees operating the Caterpillar propane gas fork lift had not been trained and evaluated since 2004. Employees used the fork lift to load the merchandise and to move materials in the shop. This condition exposed employees to struck-by hazards.
Recent events (1)
- — Z (O) $0
More inspections in this industry (NAICS 326199)
ERIE, PA—2026-07-14
CAPLUGS, LLC
CONNEAUT, OH—2026-07-13
CONTINENTAL STRUCTURAL PLASTICS
PETALUMA, CA—2026-07-10
LABCON NORTH AMERICA
KEEWATIN, MN—2026-07-09
111565 - TACKLE TAMER PRODUCTS INC
EAST FLAT ROCK, NC—2026-07-09
161517 - ELKAMET, INC.
More inspections in TX
WICHITA FALLS, TX—2026-07-16
UNITED RENTALS, INC.
SAN MARCOS, TX—2026-07-16
CASA MECHANICAL SERVICES, LTD.
CLARKSVILLE, TX—2026-07-15
SEQUOIAS TREE EXPERT LLC
EL PASO, TX—2026-07-15
SURE STEEL
CORPUS CHRISTI, TX—2026-07-15
NORTH STAR ENERGY SOLUTIONS LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336926183.