Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: WESTERN PRECAST CONCRETE, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of WESTERN PRECAST CONCRETE, INC. in 9101 ROSEWAY DR., EL PASO, TX 79917 (NAICS 327331). OSHA activity number 337330021.

Watch Western Precast Concrete, INC. — free Get an email when a new federal OSHA severe-injury report for Western Precast Concrete, INC. is published. One employer, no account, unsubscribe in one click.
Site address
9101 ROSEWAY DR.
City
EL PASO
State
TX
ZIP
79917
Mailing
P.O. BOX 17961, EL PASO, TX 79917
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327331
Employees
49
Ownership type
A

4 citations on file for this inspection.

1910.334 A02 I

Serious Gravity 5 1 instance 20 exposed
Issued
Abate by
Penalty
Initial $2975.00 · Current $1500.00 Reduced
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):    On or about November 13, 2012, a 24-foot orange extension cord running through a cut out hole on the metal roof was hard wired to a lighting fixture inside the metal tool shed. The extension cord had visible damage, bare conductors exposed. Employees were exposed to electrical shock hazards.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $2975

1910.305 G01 IV A

Serious Gravity 5 1 instance 20 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    On or about November 13, 2012, a 24-foot orange extension cord running through a cut out hole on the metal roof was hard wired to a lighting fixture inside the metal tool shed. The extension cord had visible damage, bare conductors exposed. Employees were exposed to electrical shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 5 1 instance 20 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were ran through holes in walls, ceilings, or floors:    On or about November 13, 2012, a 24-foot orange extension cord running through a cut out hole on the metal roof was hard wired to a lighting fixture inside the metal tool shed. The extension cord had visible damage, bare conductors exposed. Employees were exposed to electrical shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 J02 V

Other-than-serious 4 instances 20 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(j)(2)(v): A receptacle installed outdoors in a location protected from the weather or in other damp locations did not have an enclosure for the receptacle that was weatherproof when the receptacle was covered (attachment plug cap not inserted and receptacle covers closed):    On or about November 13, 2012, light poles 9, 10, 13 and 14 had a two outlet receptacles installed outdoors but did not have an enclosure for the receptacle that was weatherproof; all four receptacles were missing their covers. Employees were exposed to electrical shock.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View WESTERN PRECAST CONCRETE, INC.'s full OSHA safety record →