Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: CACTUS DRILLING COMPANY L.L.C. RIG 238

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of CACTUS DRILLING COMPANY L.L.C. RIG 238 in 8.5 MILES EAST HWY 67, BARNHART, TX 76930 (NAICS 213111). OSHA activity number 337447015.

Watch Cactus Drilling Company L.L.C. RIG 238 — free Get an email when a new federal OSHA severe-injury report for Cactus Drilling Company L.L.C. RIG 238 is published. One employer, no account, unsubscribe in one click.
Site address
8.5 MILES EAST HWY 67
City
BARNHART
State
TX
ZIP
76930
Mailing
8300 SW 15TH, OKLAHOMA CITY, OK 73128
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
213111
Employees
19
Ownership type
A

7 citations on file for this inspection.

1910.303 B01 I

Serious Gravity 1 1 instance 19 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $1800.00 Reduced
29 CFR 1910.303(b)(1)(i):  Safety of equipment was not determined using considerations for the suitability of installation and use in conformity with the provisions of this subdivision:  On or about November 8, 2012,  household type relocatable power strips were daisy chained to provided extra outlets in the upper dog house.  The daisy chaining of power strips created a fire hazard to workers.
Recent events (2)
  • — I (S) $1800
  • — Z (S) $3000

1910.305 G01 IV A

Serious Gravity 1 2 instances 19 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    On or about November 8, 2011, the following temporary electrical equipment was being used as fixed wiring.    a)  A portable fan was tied the electrical conduit on the ceiling of the SCR trailer.  It was energized to a SJTW orange extension cord tied the the trailer and plugged into a 110 VAC outlet in a box that is approved only for inside walls of residential construction.  These conditions created an electrical hazard to workers.  b) A surge protector was attached to the wall of the upper dog house to provide extra outlets.  It was plugged into a surge protector and used to energize the cordless phone used for communication to the company trailer.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV D

Serious Gravity 1 2 instances 19 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(D):  Flexible cords and cables were attached to building surfaces:  On or about November 8, 2012 the following 110 VAC flexible cords were attached creating an electrical hazard to employees:  1.  110 VAC surge protector was fixed to the wall, located in the upper dog house.  This temporary outlet was used to energize alarms and other temporary power strips.  2.  110 VAC SJTW orange extension cord was used to energize a temporary fan chain to electrical conduit on the ceiling of the SCR trailer.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B01 II

Serious Gravity 1 1 instance 19 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $1800.00 Reduced
29 CFR 1910.303(b)(1)(ii):  Electrical equipment was not free from recognized hazards, based on the mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided:  On or about Novermber 08, 2012 the metal condit on the roof of the mud house had a break.  The conduit fed the 110 VAC outlets in the mud house all of which were not grounded.  This condition exposed workers in the mud house to an electrical hazard.
Recent events (2)
  • — I (S) $1800
  • — Z (S) $3000

1910.304 G05

Serious Gravity 1 1 instance 19 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous and effective.    On or about November 8, 2012, the 110 VAC outlets in the mud house were not grounded.  The condition created an electrical hazard to workers using the outlets for such purposes as, but not limited to, mixing mud in the mud house.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Repeat 1 instance 19 exposed
Issued
Abate by
Penalty
Initial $1000.00 · Current $600.00 Reduced
29 CFR 1910.305(g)(2)(iii):  Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:  On or about November 8, 2012, a 110 VAC fitting plugged into a "TRIPP-LITE" surge protector did not have a strain relief device.  The plug was located in the upper dog house and created an electrical hazard.     The employer was previously cited for a violation of this Occupational Safety and  Standard or which was contained in OSHA inspection number: 312238710, Citation Number: 1, Item Number: 18b and was affirmed as a Final Order on Feburary 12, 2012, with respect to a workplace located at Rig 107, Pyote, TX 79777:
Recent events (2)
  • — I (R) $600
  • — Z (R) $1000

1910.157 E01

Other-than-serious 4 instances 19 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.157(e)(1):  The employer did not provide for the inspection, maintenance and testing of all portable fire extinguishers in the workplace:    On or about November 8, 2012, The following fire extinguishers were missing their inspection seals creating a fire hazard to oil rig workers.  A "third party" was responable for inspecting the fire extinguishers:  1.  BADGER, Z-964757 20A 120 BC fire extinguisher located at mud pits. The seal was missing.  2.  BADGER, CO2 Model B10V, Z-7329118, 10LB type BC fire extinguisher, located electrical trailer.  The seal was missing.  3.  ANUSL Sentry af-108489 20A 120BC, located in motor room.  The seal was missing.  4.  Large fire extinguisher located at the accumulators.  The seal was miissing and the label was not legible.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337447015.