AYER, MA —
OSHA Inspection: CAINS FOODS, LP
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of CAINS FOODS, LP in 114 EAST MAIN ST., AYER, MA 01432 (NAICS 311941). OSHA activity number 337688824.
Where did this inspection happen?
- Establishment
- CAINS FOODS, LP
- Site address
- 114 EAST MAIN ST.
- City
- AYER
- State
- MA
- ZIP
- 01432
- Mailing
- 114 EAST MAIN ST., AYER, MA 01432
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311941
- Employees
- 143
- Ownership type
- A
Citations
8 citations on file for this inspection.
5(a)(1)
- Issued
- Abate by
- Penalty
- Initial $3825.00 · Current $3479.00 Reduced
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to crushing hazards: (a) Location - Warehouse: On or about 12/18/12 multiple storage racks, holding pallets of mayonaisse and/or dressing product with an average weight of 1850 pounds each, had structural damage exposing employees to hazards of being struck or crushed by falling pallets and boxes.
Recent events (2)
- — I (S) $3479
- — Z (S) $3825
1910.22 D01
- Issued
- Abate by
- Penalty
- Initial $3825.00 · Current $500.00 Reduced
General-duty citation text
29 CFR 1910.22(d)(1): On every building or other structure, or part thereof, used for mercantile, business, industrial or storage purposes, the loads approved by the building official were not marked on plates of approved design and securely affixed in a conspicuous place in each space to which they relate: (a) Location - Main Building, Loading Dock On or about 12/5/2012, the load rating for the storage racks located above the loading dock overhead doors was not posted. The storage racks held pallets of rolled labels. (b) Location - Warehouse On or about 12/18/2012, the load rating for the storage racks was not posted. The storage racks held pallets of mayonaisse and dressings in boxes.
Recent events (2)
- — I (O) $500
- — Z (S) $3825
1910.147 C06 I
- Issued
- Abate by
- Penalty
- Initial $3825.00 · Current $3479.00 Reduced
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct an annual or more frequent inspection of the energy control procedure to ensure that the procedure and requirements of this standard were followed: (a) Location - Establishment On or about 12/5/2012, the employer did not conduct an annual or more frequent inspection of the Lock Out Tag Out procedures to ensure the procedures and energy control requirements were followed when cleaning, maintaining or repairing the plant equipment including, but not limited to, mixers, bottlers, and conveyors.
Recent events (2)
- — I (S) $3479
- — Z (S) $3825
1910.303 C03 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(c)(3)(i): Conductors shall be spliced or joined with splicing devices identified for the use or by brazing, welding, or soldering with a fusible metal or alloy. Soldered splices shall first be spliced or joined to be mechanically and electrically secure without solder and then soldered. All splices and joints and the free ends of conductors shall be covered with an insulation equivalent to that of the conductors or with an insulating device identified for the purpose: (a) Location - Production Area On or about 12/5/12 an electrical cord, servicing the boxing machine, was repaired with black electrical tape. (b) Location - Forklift Charging Area On or about 12/5/12 an electrical cord, servicing a powered industrial truck charger, was repaired with yellow electrical tape. (c) Location - Forklift Charging Area On or about 12/5/12 an electrical cord, servicing a powered industrial truck charger, was repaired with black electrical tape.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.303 G01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: (a) Main Plant, Forklift Charging Station On or about 12/5/12 an electrical panel box was blocked by a forklift charger.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv): Flexible cords and/ or cables were used for purposes prohibited by paragraphs (A) through (F) of 29 CFR 1910.305(g)(1)(iv): (a) Location - Warehouse On or about 12/5/12, an electrical cord powering a water cooler was run under a door to an outlet on the other side of the wall.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: (a) Location - Establishment: On or about 12/5/12 an electrical cord, powering a box machine, had exposed wire between the plug and cord where a strain relief had not been provided.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.134 K06
- Issued
- Abate by
- Penalty
- Initial $765.00 · Current $765.00
General-duty citation text
29 CFR 1910.134(k)(6): The employer did not provide the basic advisory information on respirators, as presented in Appendix D of 29 CFR 1910.134, in written or oral format to employees who wear respirators when such use was not required by the employer: (a) Location - Establishment On or about 12/5/12 the employer did not provide the information in Appendix D of 1910.134 to employees that were allowed to wear tight-fitting filtering facepiece respirators.
Recent events (2)
- — I (O) $765
- — Z (O) $765
More inspections at CAINS FOODS, LP
AYER, MA—2011-06-14 00:00:00
CAINS FOODS, LP
AYER, MA—1997-03-20 00:00:00
CAINS FOODS, LP
View CAINS FOODS, LP's full OSHA safety record →
More inspections in this industry (NAICS 311941)
CHESTER, VT—2026-06-15
DREW'S LLC
WENATCHEE, WA—2026-05-26
WA317991224 - YONDER CIDER LLC
WENATCHEE, WA—2026-05-26
WA317991243 - YONDER CIDER LLC
PARIS, TN—2026-05-20
ALLEGRO FINE FOODS, INC.
LOS BANOS, CA—2026-05-14
KAGOME INC.
More inspections in MA
BELLINGHAM, MA—2026-07-16
BELLINGHAM DEPARTMENT OF PUBLIC WORKS
PLYMOUTH, MA—2026-07-15
TECH-ETCH, INC.
WESTFIELD, MA—2026-07-15
BOISE CASCADE BUILDING MATERIALS DISTRIBUTION, L.L.C.
QUINCY, MA—2026-07-15
UNITEDWOR VM CONTRACTOR CORP
FALL RIVER, MA—2026-07-15
CRESCO LABS, INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337688824.