CHAMBERSBURG, PA —
OSHA Inspection: SHIVELY MOTORS, INC.
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of SHIVELY MOTORS, INC. in 801 LINCOLN WAY WEST, CHAMBERSBURG, PA 17202 (NAICS 441110). OSHA activity number 337826218.
Where did this inspection happen?
- Establishment
- SHIVELY MOTORS, INC.
- Site address
- 801 LINCOLN WAY WEST
- City
- CHAMBERSBURG
- State
- PA
- ZIP
- 17202
- Mailing
- 801 LINCOLN WAY WEST, CHAMBERSBURG, PA 17202
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 441110
- Employees
- 22
- Ownership type
- A
Citations
11 citations on file for this inspection.
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $2400.00 · Current $1560.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Northeast Corner of Main Service and Repair Shop On or about December 12, 2012, employees, repairing and servicing automobiles, were using non-commercially rated electrical adaptors to extend the outlet boxs plug capacity in that they were using a power strip plugged into a three-plug adaptor, neither of which were listed or labeled for commercial use. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $1560
- — Z (S) $2400
1910.305 G01 IV
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv): Flexible cords and/ or cables were used for purposes prohibited by paragraphs (A) through (F) of 29 CFR 1910.305(g)(1)(iv): a) Northwest Corner of Main Service and Repair Shop - On or about December 12, 2012, the employer used a flexible cord in place of permanent wiring, exposing employees to fire, electrical burn, and electrical shock hazards while using the hanging hand lamp to complete automotive repairs. b) Northwest Corner of Main Service and Repair Shop - On or about December 12, 2012, the employer attached flexible cords to the interior wall, exposing employees to fire, electrical burn, and electrical shock hazards while using the hanging hand lamp to complete automotive repairs. c) Parts Delivery Receiving Bay - On or about December 12, 2012, employees, checking in automobile parts deliveries, were using a flexible cord run through a hole in the wall to power the portable stereo system because there were no wall outlets, exposing employees to fire, electrical burn, and electrical shock hazards. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 F02
- Issued
- Abate by
- Penalty
- Initial $2400.00 · Current $1560.00 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) East Wall of Main Service and Repair Shop - On or about December 12, 2012, employees, repairing and servicing automobiles, were exposed to an electrical breaker box that was unmarked as to the functions of all of the breakers. b) West wall of the repurposed Auto Body Shop - On or about December 12, 2012, employees, turning on the shop lights, were exposed to an electrical breaker box that was unmarked as to the functions of all of the breakers. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $1560
- — Z (S) $2400
1910.303 G01 II
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a) East Wall of Main Service and Repair Shop - On or about December 12, 2012, employees, repairing and servicing automobiles, were exposed to the fire hazard of using the working space in front of the electrical breaker boxes for the storage of the 'A'-frame ladder and miscellaneous items. b) West wall of the repurposed Auto Body Shop - On or about December 12, 2012, employees, turning on the shop lights, were exposed to the fire and explosion hazards of using the working space in front of the electrical breaker box for the storage of the 55-gallon drum of Nason 481-16 Acrylic Lacquer Thinner, a Category 2 [Class IB] flammable liquid. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.304 F01 VIII
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD:" a) West wall of the repurposed Auto Body Shop - On or about December 12, 2012, employees, turning on the shop lights, were exposed to the fire and explosion hazards of using the breaker for a light switch in that the breaker was not designed or designated for that purpose in a classified location. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 D02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(d)(2): Panelboards were not mounted in cabinets, cutout boxes, or enclosures designed for the purpose and/or were not dead front: a) South end of the repurposed Auto Body Shop - On or about December 12, 2012, employees, repairing and servicing automobiles, were exposed to the fire hazard of an uncovered, energized electrical breaker box. b) West wall of the repurposed Auto Body Shop - On or about December 12, 2012, employees, turning on the shop lights, were exposed to the fire and explosion hazards of an uncovered, energized electrical breaker box in a classified location. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G02 I
- Issued
- Abate by
- Penalty
- Initial $2800.00 · Current $1820.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) East Wall of Main Service and Repair Shop - On or about December 12, 2012, the employer had not adequately guarded open portion of the breaker bank in the electrical breaker box against accidental contact, exposing employees, repairing and servicing automobiles, to fire, electrical burn, and electrical shock hazards. b) West wall of the repurposed Auto Body Shop - On or about December 12, 2012, employees, turning on the shop lights, were exposed to the fire and explosion hazards of electrical taped 220 volt live wires in a classified location in that the wires were inadequately guarded against accidental contact. Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (2)
- — I (S) $1820
- — Z (S) $2800
1910.307 C03
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.307(c)(3): Equipment was not safe for the location in that it was not of a type and design that the employer demonstrated would provide protection from the hazards arising from the combustibility and flammability of vapors, liquids, gases, dusts, or fibers involved: a) West wall of the repurposed Auto Body Shop - On or about December 12, 2012, employees, turning on the shop lights, were exposed to the fire and explosion hazards of electrical taped 220 volt live wires being present over the 55-gallon drum of Nason 481-16 Acrylic Lacquer Thinner, a Category 2 [Class IB] flammable liquid, a Class I, Division 2, classified location. Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.1200 E01
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $1300.00 Reduced
General-duty citation text
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met: a) In the Service Department - On or about December 12, 2012, the employer had not implemented or maintained, a written hazard communication program which at least described how the criteria specified in paragraphs (f) Labels, (g) Material Safety Data Sheets, and (h) Training was being met for employees using chemicals such as motor oils, transmission fluid, brake fluid, wiper washer fluid, and Nason 481-16 Acrylic Lacquer Thinner, a Category 2 [Class IB] flammable liquid. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $1300
- — Z (S) $2000
1910.1200 G08
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.1200(g)(8): The employer did not maintain in the workplace copies of the required safety data sheets for each hazardous chemical, and did not ensure that they were readily accessible during each work shift to employees when they were in their work area(s): a) In the Service Department - On or about December 12, 2012, the employer had not maintained at the workplace copies of the required material safety data sheets for motor oils, transmission fluid, brake fluid, wiper washer fluid, and Nason 481-16 Acrylic Lacquer Thinner, a Category 2 [Class IB] flammable liquid and had not ensured that they were readily accessible during each work shift. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.1200 H01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area: a) In the Service Department - On or about December 12, 2012, the employer had not provided employees with effective information and training on the physical and health hazards associated with the chemicals used and stored on site, including but not limited to motor oils, transmission fluid, brake fluid, wiper washer fluid, and the 55-gallon drum of Nason 481-16 Acrylic Lacquer Thinner, a Category 2 [Class IB] flammable liquid. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 441110)
SAN ANTONIO, TX—2026-07-08
NORTH PARK TOYOTA OF SAN ANTONIO
BIRMINGHAM, MI—2026-06-29
SIGNATURE ASSOCIATES, LLC
SACRAMENTO, CA—2026-06-24
MAITA TOYOTA OF SACRAMENTO
PATEROS, WA—2026-06-22
WA317991601 - COLUMBIA RIVER AUTO SALES LLC
RAYMOND, WA—2026-06-18
WA317991734 - FIVE STAR DEALERSHIPS INC
More inspections in PA
PHILADELPHIA, PA—2026-07-16
URUS CONSTRUCTION CORPORATION
JEFFERSON HILLS, PA—2026-07-16
MARATHON PETROLEUM COMPANY ASPHALT TERMINAL
SMITHFIELD, PA—2026-07-16
CARLISLE CONSTRUCTION MATERIALS
PITTSBURGH, PA—2026-07-15
DREAM GREENER LAWN & LANDSCAPE
COCHRANTON, PA—2026-07-15
CRAWFORD COUNTY HARDWOODS, LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337826218.