SOUTH HOUSTON, TX —
OSHA Inspection: DIVISION 16
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of DIVISION 16 in 1101 DALLAS STREET, SOUTH HOUSTON, TX 77587 (NAICS 238210). OSHA activity number 338227416.
Where did this inspection happen?
- Establishment
- DIVISION 16
- Site address
- 1101 DALLAS STREET
- City
- SOUTH HOUSTON
- State
- TX
- ZIP
- 77587
- Mailing
- 22820 I-45 N., SPRING, TX 77373
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 2
- Ownership type
- A
Citations
5 citations on file for this inspection.
1926.403 I02 I D
- Issued
- Abate by
- Penalty
- Initial $1200.00 · Current $720.00 Reduced
General-duty citation text
29 CFR 1926.403(i)(2)(i)(D): Live parts were not guarded by elevation of 8 feet (2.44 m) or more above the floor or other working surface and so installed as to exclude unqualified persons. At the site, where temporary lighting was in use, two lights in a closet were approximately 5 feet above the floor surface exposing to them to possible breakage and electrical hazards.
Recent events (2)
- — I (S) $720
- — Z (S) $1200
1926.405 A02 I
- Issued
- Abate by
- Penalty
- Initial $1200.00 · Current $720.00 Reduced
General-duty citation text
29 CFR 1926.405(a)(2)(i): Temporary wiring was not removed immediately upon completion of construction or the purpose for which the wiring was installed: At the site, in the building under construction, where temporary electrical wires entered the building at the southeast corner and traveled through water, exposing employees to electrical hazards.
Recent events (2)
- — I (S) $720
- — Z (S) $1200
1926.405 A02 II B
- Issued
- Abate by
- Penalty
- Initial $2800.00 · Current $1680.00 Reduced
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(B): Runs of open conductors used as temporary wiring branch circuits were located where the conductors would be subject to physical damage, or the conductors were fastened at intervals exceeding 10 feet: At the site, traveling from an adjacent existing structure's electrical panel to a building under construction, were temporary electrical wires running through broken and unfasten PVC pipes, exposing employees to electrical hazards.
Recent events (2)
- — I (S) $1680
- — Z (S) $2800
1926.405 J01 I
- Issued
- Abate by
- Penalty
- Initial $1200.00 · Current $720.00 Reduced
General-duty citation text
29 CFR 1926.405(j)(1)(i): Fixtures, lampholders, lamps, rosettes, or receptacles had live parts normally exposed to employee contact: At the site, in the building under construction, where receptacles were in use on the first and second floors, two receptacles did not have covers to prevent employees from being exposed to live parts.
Recent events (2)
- — I (S) $720
- — Z (S) $1200
1926.405 A02 II E
- Issued
- Abate by
- Penalty
- Initial $400.00 · Current $240.00 Reduced
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(E):Lamps used in temporary wiring for general illumination were not protected from accidental contact or breakage: At the site, where temporary lighting was in use, three lights did not have covers to prevent them from accidental breakage.
Recent events (2)
- — I (O) $240
- — Z (O) $400
More inspections in this industry (NAICS 238210)
SOUTH FULTON, GA—2026-07-10
REEDWICK, LLC
NIAGARA FALLS, NY—2026-07-10
GAINES ELECTRICAL CONTRACTING, INC.
OGDENSBURG, NY—2026-07-10
S & L ELECTRIC, INC.
BOISE, ID—2026-07-09
POWERHOUSE ELECTRIC INC.
LYNCHBURG, VA—2026-07-09
WHITE ELECTRICAL SERVICES LLC
More inspections in TX
SPRING, TX—2026-07-10
DORSTENER WIRE TECH INC.
FORT WORTH, TX—2026-07-10
RC PROFESSIONAL ROOFING OF TEXAS LLC
CYPRESS, TX—2026-07-10
FEDERICO CARVAJAL GARCIA
SAN ANTONIO, TX—2026-07-10
ED LONG'S METAL WORKS
SAN ANTONIO, TX—2026-07-09
WAREHOUSE RACK COMPANY, LP
Source