Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: DIVISION 16

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of DIVISION 16 in 1101 DALLAS STREET, SOUTH HOUSTON, TX 77587 (NAICS 238210). OSHA activity number 338227416.

Watch Division 16 — free Get an email when a new federal OSHA severe-injury report for Division 16 is published. One employer, no account, unsubscribe in one click.
Establishment
DIVISION 16
Site address
1101 DALLAS STREET
City
SOUTH HOUSTON
State
TX
ZIP
77587
Mailing
22820 I-45 N., SPRING, TX 77373
Inspection type
Unprogrammed Other (I)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

5 citations on file for this inspection.

1926.403 I02 I D

Serious Gravity 1 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $1200.00 · Current $720.00 Reduced
29 CFR 1926.403(i)(2)(i)(D): Live parts were not guarded by elevation of 8 feet (2.44 m) or more above the floor or other working surface and so installed as to exclude unqualified persons.    At the site, where temporary lighting was in use, two lights in a closet were approximately 5 feet above the floor surface exposing to them to possible breakage and electrical hazards.
Recent events (2)
  • — I (S) $720
  • — Z (S) $1200

1926.405 A02 I

Serious Gravity 1 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $1200.00 · Current $720.00 Reduced
29 CFR 1926.405(a)(2)(i): Temporary wiring was not removed immediately upon completion of construction or the purpose for which the wiring was installed:    At the site, in the building under construction, where temporary electrical wires entered the building at the southeast corner and traveled through water, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $720
  • — Z (S) $1200

1926.405 A02 II B

Serious Gravity 10 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1680.00 Reduced
29 CFR 1926.405(a)(2)(ii)(B): Runs of open conductors used as temporary wiring branch circuits were located where the conductors would be subject to physical damage, or the conductors were fastened at intervals exceeding 10 feet:    At the site, traveling from an adjacent existing structure's electrical panel to a building under construction, were temporary electrical wires running through broken and unfasten PVC pipes, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $1680
  • — Z (S) $2800

1926.405 J01 I

Serious Gravity 1 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $1200.00 · Current $720.00 Reduced
29 CFR 1926.405(j)(1)(i): Fixtures, lampholders, lamps, rosettes, or receptacles had live parts normally exposed to employee contact:    At the site, in the building under construction, where receptacles were in use on the first and second floors, two receptacles did not have covers to prevent employees from being exposed to live parts.
Recent events (2)
  • — I (S) $720
  • — Z (S) $1200

1926.405 A02 II E

Other-than-serious 3 instances 1 exposed
Issued
Abate by
Penalty
Initial $400.00 · Current $240.00 Reduced
29 CFR 1926.405(a)(2)(ii)(E):Lamps used in temporary wiring for general illumination were not protected from accidental contact or breakage:    At the site, where temporary lighting was in use, three lights did not have covers to prevent them from accidental breakage.
Recent events (2)
  • — I (O) $240
  • — Z (O) $400

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338227416.