Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: MARSHALL HEALTH CARE FACILITY

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of MARSHALL HEALTH CARE FACILITY in 16 BEAL ST, MACHIAS, ME 04654 (NAICS 623110). OSHA activity number 338605033.

Watch Marshall Health Care Facility — free Get an email when a new federal OSHA severe-injury report for Marshall Health Care Facility is published. One employer, no account, unsubscribe in one click.
Site address
16 BEAL ST
City
MACHIAS
State
ME
ZIP
04654
Mailing
16 BEAL ST, MACHIAS, ME 04654
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
623110
Employees
85
Ownership type
A

5 citations on file for this inspection.

1910.303 G01 I A

Serious Gravity 1 2 instances 3 exposed
Issued
Abate by
Penalty
Initial $2100.00 · Current $1575.00 Reduced
29 CFR 1910.303(g)(1)(i)(A): The depth of the working space in the direction of access to live parts may not be less than indicated in Table S-1. Distances shall be measured from the live parts if they are exposed or from the enclosure front or opening if they are enclosed;    Laundry -  The switches were less than sixteen (16) inches instead of the required thirty six (36) inches working clearance behind the dryers.
Recent events (2)
  • — I (S) $1575
  • — Z (S) $2100

1910.305 B01 II

Serious Gravity 5 3 instances 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed.  1.    Laundry - Two knockouts on the bases of the switches were not effectively closed.  2.    Boiler Room -  One knockout on the side of the main breaker panel was not effectively closed.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B01 II

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(1)(ii):   Mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided;  laundry - The right hand switch box lower right corner was held together with conductive duct tape.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 E01 II

Other-than-serious 1 instance 85 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.1200(e)(1)(ii): The methods the employer will use to inform employees of the hazards of non-routine tasks (for example, the cleaning of reactor vessels), and the hazards associated with chemicals contained in unlabeled pipes in their work areas.  Facility - The employer's written hazard communications program did not contain a section to specify the methods the employer would use to inform the employees concerning non-routine tasks.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1200 E02

Other-than-serious 1 instance 85 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.1200(e)(2): "Multi-employer workplaces." Employers who produce, use, or store hazardous chemicals at a workplace in such a way that the employees of other employer(s) may be exposed (for example, employees of a construction contractor working on-site) shall additionally ensure that the hazard communication programs developed and implemented under this paragraph (e) include the following:  Facility - The employer did not specify a means to communicate with other employers working on site how to obtain the Material Safety Data Sheets of chemicals they are exposed to, what protective measures are needed, and the labeling system used by the employer.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338605033.