OSHA Inspection: SVO PACIFIC, INC.

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of SVO PACIFIC, INC. in 6 KAI ALA DRIVE, LAHAINA, HI 96761 (NAICS 721110). OSHA activity number 338667439.

Watch SVO Pacific, INC. — free Get an email when a new federal OSHA severe-injury report for SVO Pacific, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
SVO PACIFIC, INC.
Site address
6 KAI ALA DRIVE
City
LAHAINA
State
HI
ZIP
96761
Mailing
6 KAI ALA DRIVE, LAHAINA, HI 96761
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721110
Employees
500
Ownership type
A

4 citations on file for this inspection.

1910.95 D01

Serious Gravity 5 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $5000.00 · Current $3750.00 Reduced
29 CFR 1910.95(d)(1):     When information indicated that any employee's exposure equaled or exceed the 8-hour time-weighted average of 85 decibels, the employer did not develop and implement a monitoring program:    (a) Where background noise levels in the north chiller room exceeded 93 dBA, the north mechanical room exceeded 85 dBA, and the north pump room exceeded 85 dBA The Westin Ka'anapali Ocean Resort did not implement an employee exposure monitoring program to determine if employee's 8-hour time-weighted average exceeded 85 decibels.
Recent events (2)
  • — I (S) $3750
  • — Z (S) $5000

1910.159 C10

Serious Gravity 5 1 instance 500 exposed
Issued
Penalty
Initial $4000.00 · Current $3000.00 Reduced
29 CFR 1910.159(c)(10):     The minimum vertical clearance of 18 inches between automatic sprinkler systems sprinklers and the material below was not maintained:    (a) At the Westin Ka'anapali Ocean Resort Villas in the maintenance storage area on or about January 29, 2013 the minimum vertical clearance of 18 inches between automatice sprinkler systems sprinklers and the material below was not maintained.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $4000

1910.305 B01 II

Serious Gravity 5 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $4000.00 · Current $3000.00 Reduced
29 CFR 1910.305(b)(1)(ii):     Unused openings in boxes, cabinets, or fittings were not effectively closed:       (a) At The Westin Ka'anapali Ocean Resort Villas on or about January 29, 2013 a 1" diameter opening in the 2.5" X 4" cable chase in the elevator mechanical room was not effectively closed.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $4000

1910.305 B02 I

Serious Gravity 5 3 instances 500 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(2)(i):     Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:    (a) On or about January 29, 2013 at The Westin Ka'anapali Ocean Resort Villas in the north chiller room a box on the back wall in the second room was missing a cover leaving the wiring exposed; and    (b) On or about January 29, 2013 at The Westin Ka'anapali Ocean Resort Villas in the north chiller room a box on the side wall in the second room was missing a cover leaving the wiring exposed; and    (c) On or about January 29, 2013 at The Westin Ka'anapali Ocean Resort Villas in the security office just inside the entry door an electrical cover was not attached to the junction box leaving the wiring exposed.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0