Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: SOUTHWEST ENGINEERING COMPANY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SOUTHWEST ENGINEERING COMPANY in 729 S.E. 29TH, OKLAHOMA CITY, OK 73129 (NAICS 332999). OSHA activity number 338924640.

Watch Southwest Engineering Company — free Get an email when a new federal OSHA severe-injury report for Southwest Engineering Company is published. One employer, no account, unsubscribe in one click.
Site address
729 S.E. 29TH
City
OKLAHOMA CITY
State
OK
ZIP
73129
Mailing
729 S.E. 29TH, OKLAHOMA CITY, OK 73129
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332999
Employees
2
Ownership type
A

4 citations on file for this inspection.

1910.107 B05 I

Serious Gravity 1 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $1200.00 · Current $720.00 Reduced
29 CFR 1910.107(b)(5)(i): There were no visible gauge(s), audible alarm(s) or pressure activated device(s) installed on paint spray booth to indicate or insure that the required air velocity was maintained:    On or about February 28, 2013, and times prior thereto, there were no devices installed on the paint spray booth to insure that the required air velocity was maintained.  Employees were exposed to the hazards associated with fire.
Recent events (2)
  • — I (S) $720
  • — Z (S) $1200

1910.107 C06

Serious Gravity 1 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations:    On or about February 28, 2013, and times prior thereto, the following electrical equipment located in the paint spraying area was not approved for the hazardous location.  Employees were exposed to the hazards associated with fire.     a)  Fluorescent light on west wall  b)  Cord and plug operated compressor
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.107 D05

Serious Gravity 1 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.107(d)(5): Electric motor(s) driving exhaust fan(s) for spray booth(s) were located inside the booth:      On or about February 28, 2013, and times prior thereto, the electric motor driving the exhaust fan was located inside the paint spray booth.  Employees were exposed to the hazards associated with fire..
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.134 C01 II

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.134(c)(1)(ii): The respirator program did not contain provisions for medical evaluations of employees required to use respirators:    On or about February 28, 2012, and times prior thereto, the employer did not obtain a medical evaluation of employees required to use respirators.  Employees use products such as, but not limited to, laquer thinner containing xylene.