OKLAHOMA CITY, OK —
OSHA Inspection: SOUTHWEST ENGINEERING COMPANY
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of SOUTHWEST ENGINEERING COMPANY in 729 S.E. 29TH, OKLAHOMA CITY, OK 73129 (NAICS 332999). OSHA activity number 338924640.
Where did this inspection happen?
- Establishment
- SOUTHWEST ENGINEERING COMPANY
- Site address
- 729 S.E. 29TH
- City
- OKLAHOMA CITY
- State
- OK
- ZIP
- 73129
- Mailing
- 729 S.E. 29TH, OKLAHOMA CITY, OK 73129
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332999
- Employees
- 2
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.107 B05 I
- Issued
- Abate by
- Penalty
- Initial $1200.00 · Current $720.00 Reduced
General-duty citation text
29 CFR 1910.107(b)(5)(i): There were no visible gauge(s), audible alarm(s) or pressure activated device(s) installed on paint spray booth to indicate or insure that the required air velocity was maintained: On or about February 28, 2013, and times prior thereto, there were no devices installed on the paint spray booth to insure that the required air velocity was maintained. Employees were exposed to the hazards associated with fire.
Recent events (2)
- — I (S) $720
- — Z (S) $1200
1910.107 C06
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations: On or about February 28, 2013, and times prior thereto, the following electrical equipment located in the paint spraying area was not approved for the hazardous location. Employees were exposed to the hazards associated with fire. a) Fluorescent light on west wall b) Cord and plug operated compressor
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.107 D05
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.107(d)(5): Electric motor(s) driving exhaust fan(s) for spray booth(s) were located inside the booth: On or about February 28, 2013, and times prior thereto, the electric motor driving the exhaust fan was located inside the paint spray booth. Employees were exposed to the hazards associated with fire..
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.134 C01 II
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.134(c)(1)(ii): The respirator program did not contain provisions for medical evaluations of employees required to use respirators: On or about February 28, 2012, and times prior thereto, the employer did not obtain a medical evaluation of employees required to use respirators. Employees use products such as, but not limited to, laquer thinner containing xylene.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 332999)
SMITHFIELD, UT—2026-07-16
METAL VISION INC.
MINNEAPOLIS, MN—2026-07-15
111597 - CHANDLER INDUSTRIES INC - BLAINE DIVISION
SPRING, TX—2026-07-10
DORSTENER WIRE TECH INC.
SAN ANTONIO, TX—2026-07-10
ED LONG'S METAL WORKS
HUNTINGDON VALLEY, PA—2026-07-09
METAL ALLIANCE, INC.
More inspections in OK
TULSA, OK—2026-07-15
LA UNION 7 LLC
MADILL, OK—2026-07-08
MID AMERICAN STEEL & WIRE CO., LLC
SEILING, OK—2026-06-26
GORE ENERGY
ADA, OK—2026-06-25
PAN AMERICA ELECTRIC , INC.
ADA, OK—2026-06-25
CITATION OIL & GAS CORPORATION
Source