OSHA Inspection: T & J ELECTRICAL CORPORATION

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of T & J ELECTRICAL CORPORATION in 1730 CENTRAL AVENUE, ALBANY, NY 12205 (NAICS 238210). OSHA activity number 338945363.

Watch T & J Electrical Corporation — free Get an email when a new federal OSHA severe-injury report for T & J Electrical Corporation is published. One employer, no account, unsubscribe in one click.
Site address
1730 CENTRAL AVENUE
City
ALBANY
State
NY
ZIP
12205
Mailing
636 2ND AVENUE, TROY, NY 12180
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
10
Ownership type
A

4 citations on file for this inspection.

1926.21 B02

Serious Gravity 5 1 instance 8 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $2800.00
29 CFR 1926.21(b)(2): The employer did not instruct each employee in the recognition and avoidance of unsafe condition(s) and the regulation(s) applicable to his work environment to control or eliminate any hazard(s) or other exposure to illness or injury:  a)  On or about March 8, 2013 and at times prior thereto at the work site; employees performing live electrical testing on 480V panels were not instructed in the recognition of unsafe conditions and regulations applicable to their work in that they were not wearing personal protective equipment required under 2009 NFPA 70E.
Recent events (1)
  • — Z (S) $2800

1926.28 A

Serious Gravity 5 1 instance 8 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $2800.00
29 CFR 1926.28(a): The employer did not require the wearing of appropriate personal protective equipment in all operations where there is an exposure to hazardous conditions:  a)  On or about March 8 2013 and at times prior thereto at the work site; employees performing live electrical testing on 480V panels were not using personal protective equipment for protection from arc flash hazards.
Recent events (1)
  • — Z (S) $2800

1926.95 C

Serious Gravity 5 1 instance 8 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.95(c): Personal protective equipment was not of safe design and construction for the work to be performed:  a) On or about March 8, 2013 and at times prior thereto at the work site; employees performed live electrical testing on 480V panels while wearing standard leather/cow hide work gloves; insulated rubber gloves were not used.
Recent events (1)
  • — Z (S) $0

1926.102 A01

Serious Gravity 5 1 instance 8 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.102(a)(1): Eye and face protective equipment were not used when machines or operations presented potential eye or face injury from physical, chemical, or radiation agents:  a) On or about March 8, 2013 and at times prior thereto at the work site; employees performing live electrical testing on 480V panels were not using face protective equipment for protection from arc flash hazards.
Recent events (1)
  • — Z (S) $0

View T & J ELECTRICAL CORPORATION's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338945363.