INDEPENDENCE, MO —
OSHA Inspection: WEST CONTINENTAL ENERGY SERVICES, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of WEST CONTINENTAL ENERGY SERVICES, INC. in 15802 INDUSTRIAL DRIVE, INDEPENDENCE, MO 64058 (NAICS 237120). OSHA activity number 338950686.
Where did this inspection happen?
- Establishment
- WEST CONTINENTAL ENERGY SERVICES, INC.
- Site address
- 15802 INDUSTRIAL DRIVE
- City
- INDEPENDENCE
- State
- MO
- ZIP
- 64058
- Mailing
- 15802 INDUSTRIAL DRIVE, INDEPENDENCE, MO 64058
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 237120
- Employees
- 3
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.23 D01
- Issued
- Abate by
- Penalty
- Initial $2100.00 · Current $1000.00 Reduced
General-duty citation text
29 CFR 1910.23(d)(1): Every flight of stairs having four or more risers was not equipped with standard stair railings or standard handrails as specified in paragraphs (d)(1)(i) through (v) of this section: (a) On or about January 23, 2013, a stairway having four or more risers and used to access the upper offices of the facility was not equipped with a standard handrail. Abatement certification is required for this item. Use the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET for this purpose.
Recent events (2)
- — I (O) $1000
- — Z (S) $2100
1910.23 E01
- Issued
- Abate by
- Penalty
- Initial $2100.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.23(e)(1): Standard railing(s) did not consist of top rail, intermediate rail and/or posts and/or did not have a vertical height of 42 inches (106.7 cm) nominal from upper surface of top rail to floor, platform runway, or ramp level: (a) On or about January 23, 2013, the railing on a stairway receiving platform used for access to the upper offices lacked an intermediate (mid) rail. Abatement certification is required for this item. Use the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET for this purpose.
Recent events (2)
- — I (O) $0
- — Z (S) $2100
1910.157 C01
- Issued
- Abate by
- Penalty
- Initial $2100.00 · Current $500.00 Reduced
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: (a) On or about January 23, 2013, none of the fire extinguishers in the first floor shop area were mounted, some were in unidentified areas, and at least one fire extinguisher identification sign was in an area where there was no fire extinguisher. Abatement certification is required for this item. Use the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET for this purpose.
Recent events (2)
- — I (O) $500
- — Z (S) $2100
1910.305 B01 II
- Issued
- Abate by
- Penalty
- Initial $2800.00 · Current $1000.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: (a) On or about January 23, 2013, two energized electrical outlet boxes had knockouts missing. One outlet box was located in the southwest corner of the shop, the other in the northeast corner. Abatement certification is required for this item. Use the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET for this purpose.
Recent events (2)
- — I (S) $1000
- — Z (S) $2800
1910.305 G02 III
- Issued
- Abate by
- Penalty
- Initial $4900.00 · Current $1000.00 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: (a) On or about January 24, 2013, a 220V flexible cable had pulled loose from its attachment point to a portable outlet box leaving the cable attached to the device by its internal conductors. Abatement certification is required for this item. Use the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET for this purpose.
Recent events (2)
- — I (S) $1000
- — Z (S) $4900
1910.1200 F06 I
- Issued
- Abate by
- Penalty
- Initial $2100.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.1200(f)(6)(i): Except as provided in 29 CFR 1910.1200(f)(7) and 29 CFR 1910.1200(f)(8), the employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the information required by 29 CFR 1910.1200(f)(1)(i) through 29 CFR 1910.1200(f)(1)(v): (a) On or about January 24, 2013, several 55 gallon drums and smaller containers of hazardous materials were present in the facility and unmarked as to contents or hazards. Abatement certification is required for this item. Use the CERTIFICATION OF CORRECIVE ACTION WORKSHEET for this purpose.
Recent events (2)
- — I (S) $0
- — Z (S) $2100
More inspections in this industry (NAICS 237120)
ARCADIA, FL—2026-07-14
M. G. DYESS, LLC
ODEM, TX—2026-07-09
MPG PIPELINE CONTRACTORS, LLC
FREMONT, MI—2026-07-07
ROESE PIPELINE COMPANY, INC.
BROOK PARK, OH—2026-06-30
MICHELS FOUNDATIONS - FRANKSVILLE, A DIVISION OF MICHELS CONSTRUCTION, INC.
HAZLE TOWNSHIP, PA—2026-06-24
LINDE CORPORATION
More inspections in MO
CLINTON, MO—2026-07-14
TORCHYLO BUILDERS, LLC.
KANSAS CITY, MO—2026-07-09
NIAGARA BOTTLING
MONETT, MO—2026-07-09
MONETT METALS INC.
PARKVILLE, MO—2026-07-08
SKY-TECH ROOFING, LLC.
SPRINGFIELD, MO—2026-07-07
D & C CONSTRUCTION, LLC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338950686.