Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: ST. LUKE'S VILLA

Special Programs inspection · Health discipline

On , OSHA opened a special Programs health inspection of ST. LUKE'S VILLA in 80 EAST NORTHAMPTON STREET, WILKES BARRE, PA 18701 (NAICS 623312). OSHA activity number 338958515.

Watch ST. Luke'S Villa — free Get an email when a new federal OSHA severe-injury report for ST. Luke'S Villa is published. One employer, no account, unsubscribe in one click.
Establishment
ST. LUKE'S VILLA
Site address
80 EAST NORTHAMPTON STREET
City
WILKES BARRE
State
PA
ZIP
18701
Mailing
80 EAST NORTHAMPTON STREET, WILKES BARRE, PA 18701
Inspection type
Special Programs (K)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
623312
Employees
100
Ownership type
A

3 citations on file for this inspection.

1910.305 J02 IV

Serious Gravity 1 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $2550.00 · Current $1913.00 Reduced
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location:   a) Dietary Department, 120 volt outlets used to power portable kitchen appliances, including ovens, toasters, and refrigerator, were not equipped with ground fault circuit interruption (GFCI), on or about March 15, 2013.  ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $1912.5
  • — Z (S) $2550

1910.305 B02 I

Serious Gravity 1 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  a) Dietary Department, a duplex box under the counter near the dishwasher was missing its cover, thus exposing live parts, on or about March 15, 2013.  ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 E01

Serious Gravity 1 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in wet locations were not weatherproof:  a) Dietary Department, a duplex box under the counter near the dishwasher was construction grade, with break-tab openings, and non-gasketed surfaces.  The box was not approved for usage in wet areas as defined by NFPA 70 National Electrical Code, on or about March 15, 2013.  ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338958515.