BOISE, ID —
OSHA Inspection: ENVIRO-TECH INDUSTRIES, LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ENVIRO-TECH INDUSTRIES, LLC in 11624 W PRESIDENT DR, BOISE, ID 83713 (NAICS 332710). OSHA activity number 338958564.
Where did this inspection happen?
- Establishment
- ENVIRO-TECH INDUSTRIES, LLC
- Site address
- 11624 W PRESIDENT DR
- City
- BOISE
- State
- ID
- ZIP
- 83713
- Mailing
- 11624 W PRESIDENT DR, BOISE, ID 83713
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332710
- Employees
- 34
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $1785.00 · Current $1250.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. (a) Rear shop area: on 03/14/2013 and at times prior thereto, a relocatable power tap (RPT) UL listed for household use was used to supply power to a 9.6 ampere vacuum and a 3.5 amp palm sander which exceeds 80% of the RPT ampere rating. (b) Rear shop area: on 3/14/2013 and at times prior thereto, two RPTs were connected to temporary electrical power cords rather than directly to permanent power as required by the listing and labeling. Note: Abatement certification IS required for this item.
Recent events (2)
- — I (S) $1249.5
- — Z (S) $1785
1910.305 G01 IV
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv): Flexible cords and/or cables were used for purposes prohibited by paragraphs (A) and (C) of 29 CFR 1910.305(g)(1)(iv): (a) Rear shop area: on 03/14/2013 and at times prior thereto, flexible cords were used to provide permanent power to a shop vacuum, battery chargers, and a palm sander. (b) Rear shop area: on 03/14/2013 and at times prior thereto, a flexible cord was routed through a loosened access panel to provide permanent lighting inside the protective case of a Hyundai-Kia Vertical Milling Machine, Model VX650. NOTE: Abatement certification IS required for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: (a) Rear shop area: on 03/14/2013 and at times prior thereto, the case of a Newport model 99J1 relocatable power tap cord fitting was damaged to the point that strain relief was not provided. NOTE: Abatement certification IS required for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1904.40 A
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1904.40(a): The employer did not provide an authorized government representative the records within the four business hours. (a) Establishment: On 3/14/2013 and at times prior thereto, the employer failed to provide copies of the injury and illness records to an authorized representative within the allowable time. NOTE: Abatement certification IS NOT required for this item.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 332710)
CAMBRIDGE, MN—2026-07-09
111567 - VISION MACHINE INC
SAINT PAUL, MN—2026-07-09
111558 - ST PAUL MACHINE - DESIGN INC
EVERETT, WA—2026-07-07
WA317991968 - ONOMAC INDUSTRIES INC
SOUTH DEERFIELD, MA—2026-07-07
VISION MACHINING INC
LAKEVILLE, MN—2026-07-02
111518 - KD HOLDING COMPANY INC DBA MEDFAB MANUFACTURING CO
More inspections in ID
GOODING, ID—2026-07-10
DAHLGREN INDUSTRIAL INC.
MERIDIAN, ID—2026-07-10
IDAHO HOMES CONSTRUCTION LLC
MERIDIAN, ID—2026-07-10
DIAMOND CONCRETE, LLC
BOISE, ID—2026-07-09
POWERHOUSE ELECTRIC INC.
BOISE, ID—2026-07-09
MARK GUHO CONSTRUCTION COMPANY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338958564.