Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: HORIZON AIR SERVICES INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of HORIZON AIR SERVICES INC. in 480 MCCLELLAN HWY, EAST BOSTON, MA 02128 (NAICS 484110). OSHA activity number 338980386.

Watch Horizon AIR Services INC. — free Get an email when a new federal OSHA severe-injury report for Horizon AIR Services INC. is published. One employer, no account, unsubscribe in one click.
Site address
480 MCCLELLAN HWY
City
EAST BOSTON
State
MA
ZIP
02128
Mailing
480 MCCLELLAN HWY, EAST BOSTON, MA 02128
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
484110
Employees
56
Ownership type
A

3 citations on file for this inspection.

1910.37 B02

Serious Gravity 1 1 instance 1 exposed
Issued
Penalty
Initial $1785.00 · Current $893.00 Reduced
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign wording "Exit":    Location: Warehouse Dock Area    Employer did not maintain emergency exit light so that the reading EXIT was visible.
Recent events (2)
  • — I (S) $892.5
  • — Z (S) $1785

1910.151 C

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $2800.00 · Current $0.00 Reduced
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:   Location: Warehouse area   No eye wash facility was available where battery maintenance was being performed on forklift.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2800

1910.303 G01 I

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1400.00 Reduced
29 CFR 1910.303(g)(1)(i): The dimension of the working space in the direction of access to live parts operating at 600 volts or less and likely to require examination, adjustment, servicing, or maintenance while alive was less than indicated in Table S1    Location:  Electrical panel room    Access to electrical power panel was not maintainted at 36 inches as required by Table S1.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2800