LEWISTON, ID —
OSHA Inspection: LEWIS-CLARK TERMINAL, INC.
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of LEWIS-CLARK TERMINAL, INC. in 1534 3RD AVENUE N., LEWISTON, ID 83501 (NAICS 488320). OSHA activity number 339025645.
Where did this inspection happen?
- Establishment
- LEWIS-CLARK TERMINAL, INC.
- Site address
- 1534 3RD AVENUE N.
- City
- LEWISTON
- State
- ID
- ZIP
- 83501
- Mailing
- 1534 3RD AVENUE N., LEWISTON, ID 83501
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 488320
- Employees
- 11
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.303 G02 I
- Issued
- Abate by
- Penalty
- Initial $1360.00 · Current $680.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): Maintenance Shop: The electrical junction box had an opening on top of the box that employees had the potential to access exposed conductors. This exposed employees to an electrical shock hazard from accidental contact with electrical conductors.
Recent events (2)
- — I (S) $680
- — Z (S) $1360
1910.305 B01
- Issued
- Abate by
- Penalty
- Initial $1020.00 · Current $510.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(1): Conductors entering boxes, cabinets, or fittings were not protected from abrasions: (a) Grain Lab: The electrical junction box and conduit were not properly secured with the potential to cause abrasions. This exposed employees to a possible electrical shock hazard. (b) Roof Bin 13: The electrical conduit had been dislocated and crushed from the fitting. This exposed employees to a potential shock hazard from using a damaged system.
Recent events (2)
- — I (S) $510
- — Z (S) $1020
1910.305 B02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: (a) Manlift dockside: Electrical wiring splice point by the manlift did not have a cover installed. This exposed employees to a potential shock hazard from accidental contact. (b) Bin 13 roof: The electrical receptacle outside the elevator did not have a cover installed to protect it from the elements. This exposed employees to a potential shock hazard from moisture or corrosion getting into the outlet.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1917.118 E01
- Issued
- Abate by
- Penalty
- Initial $1700.00 · Current $850.00 Reduced
General-duty citation text
29 CFR 1917.118(e)(1): Fixed ladders more than 20 feet in height were not provided with a cage, well or ladder safety device: Grain Storage: The access for the catwalk is a 30 foot ladder and does not have a cage installed. This exposed employees to fall hazards from fatigue while accessing the catwalk.
Recent events (2)
- — I (S) $850
- — Z (S) $1700
1910.303 G01 I B
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater : Grain Lab: The circuit breaker panel was blocked by tables storing grain containers. This exposed employees to a tripping hazards when trying to access the breaker panel.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1917.26 B
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1917.26(b): A first aid kit and at least one person holding a valid first aid certificate were not at the terminal when work was in progress: Terminal: No one on site was qualified and trained in first aid. This exposed employees to a delay in getting immediate first aid attention in the event of an accident.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at LEWIS-CLARK TERMINAL, INC.
LEWISTON, ID—2023-07-19 00:00:00
LEWIS-CLARK TERMINAL, INC.
LEWISTON, ID—2018-07-30 00:00:00
LEWIS-CLARK TERMINAL, INC.
LEWISTON, ID—2013-04-23 00:00:00
LEWIS-CLARK TERMINAL, INC.
View LEWIS-CLARK TERMINAL, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 488320)
RIVIERA BEACH, FL—2026-07-07
PORT CONTRACTORS SOUTHEAST, LLC
JACKSONVILLE, FL—2026-07-01
CROWLEY LINER SERVICES
SEATTLE, WA—2026-06-30
WA317991873 - SSA TERMINALS LLC
TERMINAL ISLAND, CA—2026-06-10
YUSEN TERMINALS LLC
TERMINAL ISLAND, CA—2026-06-08
APM TERMINALS PACIFIC, LLC
More inspections in ID
GOODING, ID—2026-07-10
DAHLGREN INDUSTRIAL INC.
MERIDIAN, ID—2026-07-10
IDAHO HOMES CONSTRUCTION LLC
MERIDIAN, ID—2026-07-10
DIAMOND CONCRETE, LLC
BOISE, ID—2026-07-09
POWERHOUSE ELECTRIC INC.
BOISE, ID—2026-07-09
MARK GUHO CONSTRUCTION COMPANY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339025645.