Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: GULF COAST COLD STORAGE INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of GULF COAST COLD STORAGE INC in 100 PORT ROAD, PASCAGOULA, MS 39567 (NAICS 493120). OSHA activity number 339087785.

Watch Gulf Coast Cold Storage INC — free Get an email when a new federal OSHA severe-injury report for Gulf Coast Cold Storage INC is published. One employer, no account, unsubscribe in one click.
Site address
100 PORT ROAD
City
PASCAGOULA
State
MS
ZIP
39567
Mailing
P.O. BOX 1365, PASCAGOULA, MS 39567
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493120
Employees
40
Ownership type
A

5 citations on file for this inspection.

1910.303 G01

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $4500.00 · Current $2500.00 Reduced
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:    (a) 100 Port Road in Pascagoula, MS - On or about May 21, 2013, the battery rack in the maintenance shop was 26.5 inches from the circuit breaker panel.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $4500

1910.304 G05

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $4500.00 · Current $2500.00 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:     (a) 100 Port Road in Pascagoula, MS - On or about May 21, 2013, Deslat machine number 2, in building A1, the ground wire on the motor controller was not continuous.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $4500

1910.305 G01 IV

Serious Gravity 1 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2700.00 · Current $1500.00 Reduced
29 CFR 1910.305(g)(1)(iv): Flexible cords and/ or cables were used for purposes prohibited by paragraphs (A) through (F);    (a) 100 Port Road in Pascagoula, MS - On or about May 21, 2013, in building A1, a flexible cord was used in place of permanent wiring from the electrical box mounted on the wall to the De-slat #2 machine that was fastened to the floor.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $2700

1910.305 G02 III

Serious Gravity 10 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:  (a) 100 Port Road in Pascagoula, MS - On or about May 21, 2013, the De-slat machine in the cold storage room had a defective strain relief on the motor starter.  (b) 100 Port Road in Pascagoula, MS - On or about May 21, 2013, both De-slat machines, number 1 and 2, in building A1 had a defective strain relief on the motor starter.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.307 C02 I

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $6300.00 · Current $3500.00 Reduced
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that was or could be present:    (a) 100 Port Road in Pascagoula, MS - On or about May 22, 2013, the electrical equipment and wiring on the 1000 gallon propane tank was not approved for the hazardous location.
Recent events (2)
  • — I (S) $3500
  • — Z (S) $6300

View GULF COAST COLD STORAGE INC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339087785.