Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: PCI OF VIRGINIA, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of PCI OF VIRGINIA, LLC in 5000 DEEPWATER TERMINAL, RICHMOND, VA 23234 (NAICS 488320). OSHA activity number 339120248.

Watch PCI OF Virginia, LLC — free Get an email when a new federal OSHA severe-injury report for PCI OF Virginia, LLC is published. One employer, no account, unsubscribe in one click.
Site address
5000 DEEPWATER TERMINAL
City
RICHMOND
State
VA
ZIP
23234
Mailing
5000 DEEPWATER TERMINAL, RICHMOND, VA 23234
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488320
Employees
10
Ownership type
A

3 citations on file for this inspection.

1910.303 G02 I

Serious Gravity 5 3 instances 2 exposed
Issued
Penalty
Initial $2975.00 · Current $1785.00 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more shall be guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the following means:    a.)  Port Contractors; Maintenance shop: On or about 6/11/2013, a cover plate was not provided over the energized conductors of a 120 volts wall mounted receptacle thereby exposed employees to a shock hazard.     b.)  Port Contractors; Maintenance shop: On or about 6/11/2013, the front cover plate was not installed over the live bus bars of the 240/120 volts breaker panel thereby exposed employees to a shock hazard.     c.)  Port Contractors; Maintenance shop: On or about 6/11/2013, the conductor wires of a broken male attachment plug were left in an energized 120 volts wall mounted receptacle thereby exposed employees to a shock hazard.
Recent events (2)
  • — I (S) $1785
  • — Z (S) $2975

1917.152 E02 II

Serious Gravity 1 1 instance 1 exposed
Issued
Penalty
Initial $1785.00 · Current $1071.00 Reduced
29 CFR 1917.152(e)(2)(ii): Only cable free from repair or splice for 10 feet (3 m) from the electrode holder shall be used unless insulated connectors or splices with insulating quality equal to that of the cable are provided.    a.) Port Contractors; Maintenance shop: On or about 6/11/2013, a repair was made to a welding cable by applying tape around the outer insulation within 5' of the electrode holder thereby exposed employee to a potential shock hazard.
Recent events (2)
  • — I (S) $1071
  • — Z (S) $1785

1917.26 B

Other-than-serious 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1917.26(b): A first aid kit shall be available at the terminal, and at least one person holding a valid first aid certificate shall be at the terminal when work is in progress.  a.) Port Contractors; Maintenance shop: On or about 6/11/2013, a person certified in first aid was not at the terminal while work was in progress.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339120248.