SOUTH WILLIAMSPORT, PA —
OSHA Inspection: THE KEYSTONE FRICTION HINGE COMPANY
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of THE KEYSTONE FRICTION HINGE COMPANY in 520 MATTHEWS BOULEVARD, SOUTH WILLIAMSPORT, PA 17702 (NAICS 332116). OSHA activity number 339128027.
Where did this inspection happen?
- Establishment
- THE KEYSTONE FRICTION HINGE COMPANY
- Site address
- 520 MATTHEWS BOULEVARD
- City
- SOUTH WILLIAMSPORT
- State
- PA
- ZIP
- 17702
- Mailing
- 520 MATTHEWS BOULEVARD, SOUTH WILLIAMSPORT, PA 17702
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332116
- Employees
- 54
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.304 F01 IV
- Issued
- Abate by
- Penalty
- Initial $1785.00 · Current $1339.00 Reduced
General-duty citation text
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel: (a) Northeast wall of the Press Room that separates the Press Room and Cleaning Room, 520 Matthews Boulevard, South Williamsport, PA - Employee access to overcurrent devices (electrical panels) for the overhead lights, fans, crane and auxiliary equipment was blocked by an electric stove, work bench, boxes and a drum. Employees were exposed to slips, trips and falls and the hazards associated with being unable to de-energize equipment in the event of an emergency, as observed on or about June 19, 2013. (b) Southeast wall of the Cleaning Room that separates the Cleaning Room and outside, 520 Matthews Boulevard, South Williamsport, PA - Employee access to overcurrent devices (electrical panels) for the vibratory deburring and metal cleaning equipment was blocked by a cabinet, barrels and a computer monitor. Employees were exposed to slips, trips and falls and the hazards associated with being unable to de-energize equipment in the event of an emergency, as observed on or about June 19, 2013. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation.
Recent events (2)
- — I (S) $1338.75
- — Z (S) $1785
1910.305 B02
- Issued
- Abate by
- Penalty
- Initial $2380.00 · Current $1785.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(2): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: (a) Press Room, 520 Matthews Boulevard, South Williamsport, PA: Conductors from the Cooper-Weymouth-Peterson Model SE12B Powered Straightner (Serial No. 41066) were energized (120V) and uncovered. Employees were exposed to an electrical shock hazard, as observed on or about June 19, 2013. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation.
Recent events (2)
- — I (S) $1785
- — Z (S) $2380
More inspections in this industry (NAICS 332116)
SPRINGDALE, PA—2026-04-23
TECKLANE MANUFACTURING, INC.
STRATFORD, CT—2026-02-10
BLASE MANUFACTURING COMPANY
MINNEAPOLIS, MN—2026-01-07
110505 - RAO MANUFACTURING COMPANY
PINE CITY, MN—2025-12-02
110353 - M-M MANUFACTURING INC DBA PRODUCT FABRICATORS
RICHARDSVILLE, KY—2025-08-27
68342 - CANNON AUTOMOTIVE SOLUTIONS - BOWLING GREEN INC
More inspections in PA
MILTON, PA—2026-07-10
HOMETOWN FOODS CHEF BOYARDEE CO.
SUNBURY, PA—2026-07-10
DEMPSEY UNIFORM & LINEN SUPPLY, INC
LANDISVILLE, PA—2026-07-10
FAIRVIEW DEMOLITION LLC
YORK, PA—2026-07-10
AMERICAN SPECIALTY SYSTEMS INC.
WILLIAMSPORT, PA—2026-07-10
INTERNATIONAL PAINT PROS
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339128027.