WARMINSTER, PA —
OSHA Inspection: DIGITAL MACHINE CO., INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of DIGITAL MACHINE CO., INC. in 1055 LOUIS DRIVE, WARMINSTER, PA 18974 (NAICS 332710). OSHA activity number 339130817.
Where did this inspection happen?
- Establishment
- DIGITAL MACHINE CO., INC.
- Site address
- 1055 LOUIS DRIVE
- City
- WARMINSTER
- State
- PA
- ZIP
- 18974
- Mailing
- 1055 LOUIS DRIVE, WARMINSTER, PA 18974
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332710
- Employees
- 20
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $1360.00 · Current $680.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Production Floor - On or about June 11, 2013, electrical equipment was used in a manner for which it was not listed or labeled, in that knockout boxes attached to flexible cords were suspended from the ceiling to provide power to the workstations.
Recent events (2)
- — I (S) $680
- — Z (S) $1360
1910.242 B
- Issued
- Abate by
- Penalty
- Initial $1020.00 · Current $510.00 Reduced
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.: (a) Throughout Production - On or about June 11, 2013, where compressed air was used to clean metal shavings from equipment and machinery, the air pressure was not reduced to less than 30 pounds per square inch (p.s.i.).
Recent events (2)
- — I (S) $510
- — Z (S) $1020
1910.305 G01 IV A
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) Lathe Shop - On or about June 11, 2013, the Amada Horizontal Band Saw was powered with a flexible cord which was hard wired into a junction box located on the ceiling.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.147 C07 IV
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.147(c)(7)(iv): The employer did not certify that employee training had been accomplished and kept up to date: (a) Production Floor - On or about June 11, 2013, authorized level training for employees who perform servicing and maintenance on equipment with sources of hazardous energy, to include the Amada Horizontal Bandsaw, was not certified to demonstrate completion. (b) Production Floor - On or about June 11, 2013, affected training for employees who operate equipment which are subject to servicing and maintenance and which have sources of hazardous energy, was not certified to demonstrate completion.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 332710)
WIXOM, MI—2026-07-16
MANSON MANUFACTURING LLC DBA TOMCO MANUFACTURING
CLAWSON, MI—2026-07-16
FOUR WAY INDUSTRIES INC
CLAWSON, MI—2026-07-16
FOUR WAY INDUSTRIES INC
CLARKLAKE, MI—2026-07-15
CLARKLAKE MACHINE INC
MUSKEGON HEIGHTS, MI—2026-07-15
L. THOMPSON COMPANY LLC DBA TOTAL QUALITY MACHINING
More inspections in PA
PHILADELPHIA, PA—2026-07-16
URUS CONSTRUCTION CORPORATION
JEFFERSON HILLS, PA—2026-07-16
MARATHON PETROLEUM COMPANY ASPHALT TERMINAL
SMITHFIELD, PA—2026-07-16
CARLISLE CONSTRUCTION MATERIALS
PITTSBURGH, PA—2026-07-15
DREAM GREENER LAWN & LANDSCAPE
COCHRANTON, PA—2026-07-15
CRAWFORD COUNTY HARDWOODS, LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339130817.