CORNING, NY —
OSHA Inspection: JMG CONSTRUCTION CORPORATION
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of JMG CONSTRUCTION CORPORATION in RAIL YARD AT HIGH STREET, CORNING, NY 14830 (NAICS 237990). OSHA activity number 339141228.
Where did this inspection happen?
- Establishment
- JMG CONSTRUCTION CORPORATION
- Site address
- RAIL YARD AT HIGH STREET
- City
- CORNING
- State
- NY
- ZIP
- 14830
- Mailing
- 223 PORTER ROAD, POTTSTOWN, PA 19464
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 237990
- Employees
- 30
- Ownership type
- A
Citations
6 citations on file for this inspection.
1926.21 B02
- Issued
- Abate by
- Penalty
- Initial $4900.00 · Current $3920.00 Reduced
General-duty citation text
29 CFR 1926.21(b)(2): The employer did not instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his/her environment to control or eliminate any hazards or other exposure to illness or injury: a) On or about 6/17/2013, Norfolk Southern Siding: An Employee was not provided with training regarding the recognition, avoidance or abatement of hazards associated with working on electrical distribution systems. Abatement documentation is required for this item.
Recent events (2)
- — I (S) $3920
- — Z (S) $4900
1926.950 C01 I
- Issued
- Abate by
- Penalty
- Initial $4900.00 · Current $3920.00 Reduced
General-duty citation text
29 CFR 1926.950(c)(1)(i): Employees were not insulated or guarded from the energized parts with gloves and sleeves rated for the voltage involved. a) On or about 6/17/2013, Norfolk Southern Siding: An employee in proximity to the transformer feeding a lighting circuit was not wearing any protective equipment, such as, but not limited to electrical insulated gloves with sleeves. Abatement documentation is required for this item.
Recent events (2)
- — I (S) $3920
- — Z (S) $4900
1926.950 D01 III
- Issued
- Abate by
- Penalty
- Initial $4900.00 · Current $3920.00 Reduced
General-duty citation text
29 CFR 1926.950(d)(1)(iii): After all designated switches and disconnectors have been opened, rendered inoperable, and tagged, visual inspection or tests were not conducted to insure that equipment or lines have been de-energized: a) On or about 6/17/2013, Norfolk Southern Siding: Testing of the transformer and power supplying the transformer feeding the lighting circuit was not conducted prior to performing work.
Recent events (2)
- — I (S) $3920
- — Z (S) $4900
1926.954 A
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.954(a): All conductors and equipment were not treated as energized until tested or otherwise determined to be deenergized or until grounded: a) On or about 6/17/2013, Norfolk Southern Siding: All of the conductors were not treated as energized until tested or grounded. Abatement documentation is required for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.951 C01
- Issued
- Abate by
- Penalty
- Initial $4900.00 · Current $3920.00 Reduced
General-duty citation text
29 CFR 1926.951(c)(1): Portable conductive ladder(s) were used near energized lines or equipment: a) On or about 6/17/2013, Norfolk Southern Siding: An alumiinum extension ladder was used while perfoming work on a transformer feeding a lighting circuit, which was not de-energized. Abatement documentation is required for this item.
Recent events (2)
- — I (S) $3920
- — Z (S) $4900
1926.1053 B10
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.1053(b)(10): The tops of a non-self-supporting ladder were not placed with the two rails supported equally: a) On or about 6/17/2013, Norfolk Southern Siding: An aluminum extension ladder which was not equipped with a single support attachment, was used with a top rung placed against a utility pole. Abatement documentation is required for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 237990)
HARTFORD CITY, IN—2026-07-10
WHITE CONSTRUCTION
NAUGATUCK, CT—2026-07-08
WHITING-TURNER LCT2 JOINT VENTURE
SAN LEANDRO, CA—2026-07-07
SHIMMICK CONSTRUCTION COMPANY, INC
FIRCREST, WA—2026-07-07
WA317991974 - CONTINENTAL DIRT CONTRACTORS
STEVENSVILLE, MD—2026-07-07
KOKOSING INDUSTRIAL, INC.
More inspections in NY
MAYVILLE, NY—2026-07-16
MAYVILLE VILLAGE DPW
NEW HYDE PARK, NY—2026-07-16
NORTH HEMPSTEAD TN MICHAEL J TULLY PARK
CONESUS, NY—2026-07-16
CONESUS TN HIGHWAY DEPT
COMSTOCK, NY—2026-07-15
NYSDOCCS WASHINGTON CORRECTIONAL FACILITY
BALDWINSVILLE, NY—2026-07-15
LYSANDER TOWN HIGHWAY DEPARTMENT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339141228.