SEWAREN, NJ —
OSHA Inspection: SUNOCO INC. CO-OP 7014
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of SUNOCO INC. CO-OP 7014 in MILEPOST 92.9 N NJ TURNPIKE GROVER CLEVELAND PLAZA#7014, SEWAREN, NJ 07077 (NAICS 447110). OSHA activity number 339208670.
Where did this inspection happen?
- Establishment
- SUNOCO INC. CO-OP 7014
- Site address
- MILEPOST 92.9 N NJ TURNPIKE GROVER CLEVELAND PLAZA#7014
- City
- SEWAREN
- State
- NJ
- ZIP
- 07077
- Mailing
- 1 MERIDIAN BLVD., WYOMISSING, PA 19610
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 447110
- Employees
- 35
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.141 B01 I
- Issued
- Penalty
- Initial $2550.00 · Current $1912.00 Reduced
General-duty citation text
29 CFR 1910.141(b)(1)(i): Potable water was not provided in all places of employment, for drinking, washing of the person, cooking, washing of foods, washing of cooking or eating utensils, washing of food preparation or processing premises, and personal: a) Sunoco, Inc. / Grover Cleveland Plaza #7014 Sewaren, NJ site - Site Wide: Employees were not provided potable water for drinking and washing their hands from February 2013 to May 2013. Condition noted on or about 7/18/2013.
Recent events (2)
- — I (S) $1912
- — Z (S) $2550
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $3400.00 · Current $2550.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Sunoco, Inc. / Grover Cleveland Plaza #7014 Sewaren, NJ site - Site Wide: The computers used inside the building are supplied power through a series of four (4) daisy chained electrical power supplies (surge protectors) which are fed from an extension cord which is wired directly into the building's electrical system which is also fed via the Magnum generator. Condition noted on or about 7/18/2013.
Recent events (2)
- — I (S) $2550
- — Z (S) $3400
1910.303 G02 I
- Issued
- Abate by
- Penalty
- Initial $5100.00 · Current $5100.00
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) Sunoco, Inc. / Grover Cleveland Plaza #7014 Sewaren, NJ site - Site Wide: The light fixtures located inside the diesel fuel kiosk have exposed electrical wiring. Condition noted on or about 7/18/2013.
Recent events (2)
- — I (S) $5100
- — Z (S) $5100
1910.305 B01 II
- Issued
- Abate by
- Penalty
- Initial $3400.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) Sunoco, Inc. / Grover Cleveland Plaza #7014 Sewaren, NJ site - Main Kiosk electrical panels: Several electrical outlet boxes were missing knockouts. Condition noted on or about 07/18/2013.
Recent events (2)
- — I (S) $0
- — Z (S) $3400
1910.304 G05
- Issued
- Penalty
- Initial $3400.00 · Current $1700.00 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a) Sunoco, Inc. / Grover Cleveland Plaza #7014 Sewaren, NJ site - Site Wide: An extension cord, which was used to power an overhead light fixture, was not continuous, in that, the grounding pin was missing. Condition noted on or about 7/18/2013.
Recent events (2)
- — I (O) $1700
- — Z (S) $3400
1910.305 A02 I
- Issued
- Abate by
- Penalty
- Initial $4250.00 · Current $3187.00 Reduced
General-duty citation text
29 CFR 1910.305(a)(2)(i): Temporary electrical power and lighting installations 600 volts, nominal, or less were used in prohibited manners:Note: Temporary electrical power and lighting installations may only be used as specified by 1910.305(a)(2)(i)(A) through 1910.305(a)(2)(i)(C). Sunoco, Inc. / Grover Cleveland Plaza #7014 Sewaren, NJ site: a) An extension cord is being used to provided power to the portable trailer in lieu of permanent wiring. b) An extension cord is being used to provide power to the computers located in office via four (4) daisy chained power strips (surge protectors). Condition noted on or about 7/18/2013.
Recent events (2)
- — I (S) $3187
- — Z (S) $4250
More inspections in this industry (NAICS 447110)
ANCHORAGE, AK—2026-07-10
AK, INC
MURFREESBORO, TN—2026-07-09
SPEEDWAY LLC
SEATAC, WA—2026-07-07
WA317991965 - SEATAC EXPRESS INC
JACKSON, MN—2026-07-07
111538 - STAPLES ENTERPRISES INC
SALEM, OR—2026-06-30
317744532 - SALEM OIL LLC
More inspections in NJ
FREEHOLD, NJ—2026-07-10
MARIO & SONS CONSTRUCTION GROUP, LLC
FREEHOLD, NJ—2026-07-10
VACCA ROOFING
FREEHOLD, NJ—2026-07-10
SPECTRA PAINTING, INC
FREEHOLD, NJ—2026-07-10
CRAIG'S MASONRY & HARDSCAPE LLC
FREEHOLD, NJ—2026-07-10
GTN CONSTRUCTION INC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339208670.