On , OSHA opened a complaint safety inspection of STERLING SCREW MACHINE PRODUCTS in 384 CHRISTIAN LANE, KENSINGTON, CT 06037 (NAICS 332721). OSHA activity number 339222838.
Where did this inspection happen?
- Establishment
- STERLING SCREW MACHINE PRODUCTS
- Site address
- 384 CHRISTIAN LANE
- City
- KENSINGTON
- State
- CT
- ZIP
- 06037
- Mailing
- 384 CHRISTIAN LANE, KENSINGTON, CT 06037
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332721
- Employees
- 15
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.178 L01 II
- Issued
- Abate by
- Penalty
- Initial $3600.00 · Current $1800.00 Reduced
General-duty citation text
29 CFR 1910.178(l)(1)(ii): The employer did not ensure that each operator had successfully completed the training required by paragraph (l), except as permitted by paragraph (l)(5), prior to permitting an employee to operate a powered industrial truck: On or about July 24, 2013, the employer had not provided initial powered industrial truck training prior to allowing an employee to operate the company's electric pallet jacks.
Recent events (2)
- — I (S) $1800
- — Z (S) $3600
1910.178 L04 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.178(l)(4)(iii): An evaluation of each powered industrial truck operator's performance was not being conducted at least once every three years: On or about July 24, 2013, powered industrial truck operators had not had their performance or skill evaluated within three years.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.242 B
- Issued
- Abate by
- Penalty
- Initial $2700.00 · Current $1350.00 Reduced
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.: On or about July 24, 2013, Shop: Compressed air used for cleaning at the work bench near the New Britain Gridley screw machine, S/N 27514, was not reduced to below 30 p.s.i.
Recent events (2)
- — I (S) $1350
- — Z (S) $2700
1910.303 B02
- Issued
- Penalty
- Initial $3060.00 · Current $1530.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: On or about July 24, 2013, in the Main Office: A. A Sharp Carousel microwave oven was powered through a relocatable power tap. Listing and labeling instructions require the equipment be powered through a wall outlet. B. A Power Sentry relocatable power tap was used to power a Sharp Carousel microwave oven. Listing and labeling instructions state that relocatable power taps are intended to provide outlet receptacles for computers, audio and video equipment and other low voltage equipment.
Recent events (2)
- — I (S) $1530
- — Z (S) $3060
1910.304 B04 II B
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle may not supply a total cord- and plug-connected load in excess of the maximum specified in Table S-4: On or about July 24, 2013, Main Office: A 15-amp relocatable power tap was used to energize a Sharp Carousel Model R308YK, 13-amp Microwave Oven. The power tap was subject to damage from being overloaded.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01
- Issued
- Penalty
- Initial $3825.00 · Current $1913.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: On or about July 24, 2013, in the following locations, the working space before electrical equipment was blocked by storage: A. Shipping/Receiving: The works space in front of a 120V GE Powermark Gold Load Center was blocked by barrels of waste oil. B. Storage Area, behind Bridgeport manual milling machine: The work space in front of a Siemens 3-phase Indoor Load Center was blocked by the storage of a rolling cart of parts.
Recent events (2)
- — I (S) $1912.5
- — Z (S) $3825
More inspections at STERLING SCREW MACHINE PRODUCTS
KENSINGTON, CT—2011-04-29 00:00:00
STERLING SCREW MACHINE PRODUCTS
KENSINGTON, CT—2005-12-27 00:00:00
STERLING SCREW MACHINE PRODUCTS
View STERLING SCREW MACHINE PRODUCTS's full OSHA safety record →
More inspections in this industry (NAICS 332721)
NEW ULM, MN—2026-06-24
111459 - SOUTHERN MINNESOTA TOOLING INC
MARION, NY—2026-06-12
MARION MACHINE MANUFACTURERS
ARCADE, NY—2026-05-26
DEVIN MFG., INC.
SANTA FE SPRINGS, CA—2026-05-21
LEFIELL MANUFACTURING
BELLINGHAM, MA—2026-04-30
GRAYCER SCREW PRODUCTS CO., INC.
More inspections in CT
ENFIELD, CT—2026-07-16
MOMS ENFIELD
DAYVILLE, CT—2026-07-16
HARBOR FREIGHT
NEW BRITAIN, CT—2026-07-14
JANANII, LLC
NEWINGTON, CT—2026-07-14
TRUSS MANUFACTURING INC
NORTH BRANFORD, CT—2026-07-14
NYK STATEWIDE MOLINA CONSTRUCTION LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339222838.