Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: KOCH NITROGEN COMPANY, LLC

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of KOCH NITROGEN COMPANY, LLC in 11559 U.S. HWY 50, DODGE CITY, KS 67801 (NAICS 325311). OSHA activity number 339238396.

Watch Koch Nitrogen Company, LLC — free Get an email when a new federal OSHA severe-injury report for Koch Nitrogen Company, LLC is published. One employer, no account, unsubscribe in one click.
Site address
11559 U.S. HWY 50
City
DODGE CITY
State
KS
ZIP
67801
Mailing
P.O. BOX 1337, DODGE CITY, KS 67801
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325311
Employees
71
Ownership type
A

3 citations on file for this inspection.

1910.37 B01

Deleted Serious Gravity 10 1 instance 65 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $0.00 Reduced
29 CFR 1910.37(b)(1): 29 CFR 1910.37(b)(1): Each exit route was not adequately lighted so that employees with normal vision could see along the exit route:       On or about July 19, 2013 employees of Decker Electric, Inc. installing wiring for Koch Nitrogen Company, LLC and employees of Koch Nitrogen Company, LLC were exposed to hazards associated with emergency egress such as, but not limited to, inhalation hazards from ammonia, chlorine and NOx and slip and trip hazards.  On a total loss of power to the facility there was no emergency lighting along the egress routes outside of buildings to the evacuation points.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7000

1910.119 E03 VII

Other-than-serious Gravity 10 1 instance 65 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $7000.00
29 CFR 1910.119(e)(3)(vii): The process hazard analysis did not address a qualitative evaluation of a range of the possible safety and health effects of failure of controls on employees in the workplace:        On or about July 19, 2013 employees of Decker Electric, Inc. installing wiring for Koch Nitrogen Company, LLC and employees of Koch Nitrogen Company, LLC were exposed to inhalation hazards from releases or emissions of NOx.  The process hazard analysis did not consist of an evaluation of the expected exposure to employees of NOx and tail gas out of stack 221 during a loss of power/loss of flow to the absorber scenario and any engineering controls to continue combustion of these gases to prevent these exposures.
Recent events (2)
  • — I (O) $7000
  • — Z (S) $7000

1910.119 H02 II

Deleted Serious Gravity 10 1 instance 65 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $0.00 Reduced
29 CFR 1910.119(h)(2)(ii): 29 CFR 1910.119(h)(2)(ii):  The employer did not inform contract employees of potential fire, explosion or toxic release hazards related to working on or near a covered process:      On or about July 19, 2013 and July 22, 2013 employees of Decker Electric ,Inc. installing wiring for Koch Nitrogen Company, LLC were exposed to inhalation hazards from chemicals such as, but not limited to, ammonia, chlorine and NOx.  The orientation training provided to contractor employees did not completely train employees of the hazards that could be encountered while working in the facility.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7000

View KOCH NITROGEN COMPANY, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339238396.