BELLEVILLE, IL —
OSHA Inspection: DIOCESE OF BELLEVILLE SAINT PETER'S CATHEDRAL
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of DIOCESE OF BELLEVILLE SAINT PETER'S CATHEDRAL in 200 WEST HARRISON STREET, BELLEVILLE, IL 62220 (NAICS 813110). OSHA activity number 339294431.
Where did this inspection happen?
- Establishment
- DIOCESE OF BELLEVILLE SAINT PETER'S CATHEDRAL
- Site address
- 200 WEST HARRISON STREET
- City
- BELLEVILLE
- State
- IL
- ZIP
- 62220
- Mailing
- 200 WEST HARRISON STREET, BELLEVILLE, IL 62220
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 813110
- Employees
- 25
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.332 B01
- Issued
- Abate by
- Penalty
- Initial $2800.00 · Current $1680.00 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: An employee performing electrical work was exposed to an arc flash due to working on an energized 208/120 volt switch box, and the employer did not train employees regarding the requirement for safety related work practices, electrical protective equipment, and other protective requirements.
Recent events (2)
- — I (S) $1680
- — Z (S) $2800
1910.335 A01 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: On or about May 25, 2013, an employee performing electrical work was exposed to an arc flash from a 208/120 volt switch box, and the employer did not provide arc rated protective clothing such as but not limited to arc-rated long sleeve shirt and pants (or an arc rated coverall), arc-rated face-shield, or arc flash suit hood, arc-rated hard hat liner.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.333 A01
- Issued
- Abate by
- Penalty
- Initial $4200.00 · Current $2520.00 Reduced
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not de energized before the employee worked on or near them: On or about May 25, 2013, an employee was exposed to an arc flash from a 208/120 volt switch box, and the employer did not ensure that the switch was de energized before the employee worked on it.
Recent events (2)
- — I (S) $2520
- — Z (S) $4200
1910.333 B01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
The employer did not ensure that exposed de energized parts were locked out and tagged in accordance with paragraph (b) and treated them as energized parts: On or about May 25, 2013, an employee was exposed to an arc flash from a 208/120 volt switch box, and the employer did not ensure that the switch was de energized in accordance with a procedure to lock or tag out the de energized circuit(s).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.333 B02 IV
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.333(b)(2)(iv): Qualified persons did not use test equipment to test the circuit elements and electrical parts of equipment to which employees were exposed and verify the circuit elements and equipment parts were de energized. On or about May 25, 2013, an employee was exposed to an arc flash from a 208/120 volt switch box, and the employer did not ensure that test equipment was used to test the box to verify the equipment was de energized.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 813110)
LEONARD, MI—2026-07-02
THE SALVATION ARMY ECHO GROVE CAMP AND RETREAT CENTER
COLUMBIA, MD—2026-06-23
FIRST PRESBYTERIAN CHURCH OF HOWARD COUNTY, ELLICOTT CITY, MARYLAND OF THE UNITED PRESBYTERIAN CHURCH IN THE UNITED STATES OF AMERICA
RUTLAND, VT—2026-06-17
VERMONT CATHOLIC CHARITIES, INC.
SAN ANTONIO, TX—2026-05-21
ARCHDIOCESE OF SAN ANTONIO
SAN DIEGO, CA—2026-05-19
ISLAMIC CENTER OF SAN DIEGO
More inspections in IL
DEERFIELD, IL—2026-07-16
JOHN BURNS CONSTRUCTION COMPANY, LLC
BANNOCKBURN, IL—2026-07-16
BUILDER SERVICES GROUP, INC. DBA CJ INSULATION
BANNOCKBURN, IL—2026-07-16
ROOFING H.P. LLC
HIGHLAND PARK, IL—2026-07-16
UNITED PLUMBING AND DRAIN, INC.
FRANKLIN PARK, IL—2026-07-16
B & M PLASTIC INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339294431.