Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: CHEMBIO SHELTER, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of CHEMBIO SHELTER, INC. in 550 ROBERT C. BYRD DRIVE, SOPHIA, WV 25921 (NAICS 333131). OSHA activity number 339296253.

Watch Chembio Shelter, INC. — free Get an email when a new federal OSHA severe-injury report for Chembio Shelter, INC. is published. One employer, no account, unsubscribe in one click.
Site address
550 ROBERT C. BYRD DRIVE
City
SOPHIA
State
WV
ZIP
25921
Mailing
P.O. BOX 400, SOPHIA, WV 25921
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
333131
Employees
11
Ownership type
A

5 citations on file for this inspection.

1910.101 B

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $1200.00 Reduced
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6:     (a) Cylinder Storage Area: Oxygen cylinders were stored next to the opening of a garage bay door and were not secured to prevent falling, as observed on or about 08/14/2013.    ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $1200
  • — Z (S) $2000

1910.253 B02 II

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.253(b)(2)(ii):       Assigned storage spaces for cylinders was not located away from elevators, stairs, or gangways where cylinders could not be knocked over or damaged by passing or falling objects, or subject to tampering by unauthorized persons:       (a) Cylinder Storage Area: Oxygen cylinders were stored next to the opening of a garage bay door. The cylinders were not protected from being knocked over or damaged by passing employees and/or vehicles, as observed on or about 08/14/2013.       ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.253 B02 IV

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.253(b)(2)(iv): Valve protection caps, where cylinders were designed to accept caps, were not always in place, hand-tight, except when cylinders were in use or connected for use:     (a) Cylinder Storage Area: Oxygen cylinders were stored next to the opening of a garage bay door and did not have a valve protection cap, as observed on or about 08/14/2013.     ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.22 D01

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.22(d)(1): On every building or other structure, or part thereof, used for mercantile, business, industrial or storage purposes, the loads approved by the building official were not marked on plates of approved design and securely affixed in a conspicuous place in each space to which they relate.  (a) Main Shop: Employee(s) were using the roof of an employee bathroom, inside the Main Shop, as a storage area for various objects such as but not limited to tires. The storage area did not have the load rating marked and the load rating was not known, as determined on or about 08/14/2013.  ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1200 E01

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met:   (a) ChemBio Shelter, Inc.: The employer had not developed a written chemical hazard communication program for employees who use hazardous chemicals including, but not limited to, Diesel Fuel, as determined on or about 08/14/2013.   ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339296253.