RENO, NV —
OSHA Inspection: NEVADA ARMY NATIONAL GUARD, AVIONICS DIVISION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NEVADA ARMY NATIONAL GUARD, AVIONICS DIVISION in 20000 ARMY AVIATION DRIVE, RENO, NV 89506 (NAICS 488190). OSHA activity number 339299885.
Where did this inspection happen?
- Establishment
- NEVADA ARMY NATIONAL GUARD, AVIONICS DIVISION
- Site address
- 20000 ARMY AVIATION DRIVE
- City
- RENO
- State
- NV
- ZIP
- 89506
- Mailing
- 20000 ARMY AVIATION DRIVE, RENO, NV 89506
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 488190
- Employees
- 25
- Ownership type
- D
Citations
7 citations on file for this inspection.
1910.36 G02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. (a) On or about August 6, 2013, in the maintenance supervisor's and instructor's office spaces, the exit/egress was 21 and 22 inches and obstructed by a desk and pelican cases.
Recent events (1)
- — Z (S) $0
1910.37 B02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": (a) On or about August 6, 2013, in the maintenance control quality assurance office and briefing room area, exit doors were not labeled or marked "EXIT".
Recent events (1)
- — Z (S) $0
1910.157 C01
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries. (a) On or about August 6, 2013, in the supply room area, a portable fire extinguisher was free standing on a metal cabinet. (b) On or about August 6, 2013, in the supply room area, a portable fire extinguisher was obstructed by a large plastic container.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling. (a) On or about August 6, 2013, in the battery, tools and parts room. re-locatable power taps were used to plug-in a Cevalia coffee maker and other high powered appliances.
Recent events (1)
- — Z (S) $0
1910.303 F02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident. (a) On or about August 6, 2013, in the avionics shop control power panel, some of the circuit breakers were not labeled for their purpose.
Recent events (1)
- — Z (S) $0
1910.305 B02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy. (a) On or about August 6, 2013, in the avionics shop, north wall, an electrical outlet did not have a cover.
Recent events (1)
- — Z (S) $0
1910.305 G02 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws. (a) On or about August 6, 2013, in the petroleum shop room #158, the Aqua Glow water detector power cord did not have strain relief and the insulation was separating from the outer sheath.
Recent events (1)
- — Z (S) $0
More inspections in this industry (NAICS 488190)
TRAVERSE CITY, MI—2026-07-14
UNIFI AVIATION LLC
VANDALIA, OH—2026-07-08
SIERRA NEVADA CORPORATION
ASPEN, CO—2026-06-17
ATLANTIC AVIATION-MONTROSE LLC
GULF SHORES, AL—2026-06-17
TREGO/DUGAN AVIATION OF GRAND ISLAND, INC.
LOS ANGELES, CA—2026-06-12
UNITED AIRLINES
More inspections in NV
RENO, NV—2026-07-16
DC MASONRY
CARSON CITY, NV—2026-07-16
LT BUILDERS
ZEPHYR COVE, NV—2026-07-16
DOLLAR TREE STORES, INC.
SPARKS, NV—2026-07-16
SYUFY ENTERPRISES
CARSON CITY, NV—2026-07-16
UNKNOWN/INVALID ESTABLISHMENT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339299885.