On , OSHA opened a planned safety inspection of PRATT (MISSISSIPPI BOX), INC in 2031 NW PROGRESS PARKWAY, JACKSON, MS 39213 (NAICS 322211). OSHA activity number 339301103.

Watch Pratt (Mississippi BOX), INC — free Get an email when a new federal OSHA severe-injury report for Pratt (Mississippi BOX), INC is published. One employer, no account, unsubscribe in one click.
Site address
2031 NW PROGRESS PARKWAY
City
JACKSON
State
MS
ZIP
39213
Mailing
2031 NW PROGRESS PARKWAY, JACKSON, MS 39213
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
322211
Employees
48
Ownership type
A

5 citations on file for this inspection.

1910.242 B

Serious Gravity 1 3 instances 3 exposed
Issued
Abate by
Penalty
Initial $2250.00 · Current $1125.00 Reduced
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 psi.:    2031 NW Progress Parkway in Jackson, MS - On or about August 13, 2013, the air pressure exiting air nozzles used for cleaning was not reduced to 30 psi or less at;    (a) At #130 McKinley Die Cutter, the air pressure measured greater than 100 psi.  (b) At the cardboard bailer, the air pressure measured greater than 100 psi.  (c) In the maintenance area, the air pressure measured greater than 70 psi.
Recent events (2)
  • — I (S) $1125
  • — Z (S) $2250

1910.305 B01 II

Serious Gravity 1 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $1500.00 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    (a) 2031 NW Progress Parkway in Jackson, MS - On or about August 13, 2013, there were two unused openings in the control panel cabinet mounted on the cardboard compactor.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $3000

1910.307 C02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the class of location:  (a) 2031 NW Progress Parkway in Jackson, MS - On or about August 13, 2013, there were two unused openings in the control panel cabinet mounted on the cardboard compactor that was not sealed to prevent class II combustible cardboard dust from entering.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.22 A01

Deleted Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition.  (a) 2031 NW Progress Parkway in Jackson, MS - On or about August 13, 2013, the cardboard bailer and the surrounding area was not kept clean of combustible dust.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 F02

Other-than-serious 1 instance 26 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  (a) 2031 NW Progress Parkway in Jackson, MS - On or about August 13, 2013, the circuit breaker panel CLD had 6 breakers labeled, "Receptacles throughout plant", and did not mark its specific purpose.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339301103.