Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: POSKIN FEED STORE INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of POSKIN FEED STORE INC. in 968 14TH AVE, POSKIN, WI 54812 (NAICS 424510). OSHA activity number 339357741.

Watch Poskin Feed Store INC. — free Get an email when a new federal OSHA severe-injury report for Poskin Feed Store INC. is published. One employer, no account, unsubscribe in one click.
Site address
968 14TH AVE
City
POSKIN
State
WI
ZIP
54812
Mailing
968 14TH AVE, POSKIN, WI 54812
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424510
Employees
6
Ownership type
A

7 citations on file for this inspection.

1910.27 D01 IV

Serious Gravity 5 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $1400.00 Reduced
29 CFR 1910.27(d)(1)(iv): Cages shall extend down the ladder to a point not less than 7 feet nor more than 8 feet above the base of the ladder, with bottom flared not less than 4 inches, or portion of cage opposite ladder shall be carried to the base:  (a) Poskin Feed Store, Grain Bin Area; Cages on fixed ladders did not extend down the ladder to a point not less than 7 feet nor more than 8 feet above the base of the ladder, such as, but not limited to:  (1) The outside leg ladder, and   (2) The 25,000 bushel bin ladder.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2000

1910.303 B01

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $1400.00 Reduced
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees:  (a) Poskin Feed Store, ladder area of 30,000 bushel grain bin; Employees were exposed to an unprotected open electrical splice while operating the temporary discharge auger.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2000

1910.303 B07

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(7):  Electrical equipment was not installed in a neat and workmanlike manner:  (a) Poskin Feed Store, ladder area of 30,000 bushel grain bin; The temporary wiring and splices energizing equipment on the 30,000 bushel bin was strung through and wrapped around structural members of the grain bins creating an open electrical hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 C03 I

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(c)(3)(i): Conductors were not spliced or joined with splicing devices identified for the use or by brazing, welding, or soldering with a fusible metal or alloy. All splices and joints and the free ends of conductors were not covered with an insulation equivalent to that of the conductors or with an insulating device identified for the purpose:  (a) Poskin Feed Store, ladder area of 30,000 bushel grain bin; The splice in the wiring for the temporary discharge auger was created by twisting the non-insulated ends of the copper conductors together.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  (a) Poskin Feed Store, ladder area of 30,000 bushel grain bin; The open conductors energizing the temporary discharge auger were not protected by an approved junction box, cabinet or elevation.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.134 C02 I

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.134(c)(2)(i): Respirator users were not provided with the information contained in Appendix D to 29 CFR 1910.134 when the employer determined that any voluntary respirator use was permissible:   (a) Poskin Feed Store; Employees used N95 type filtering face pieces on a voluntary bases and were not informed of the required information in Appendix D.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.272 M03

Other-than-serious 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.272(m)(3): A certification record maintained of each inspection by the employer in the grain facility was not in accordance with 29 CFR 1910.272(1):   (a) Posking Feed Store, office; A certification of maintenance inspections was not maintained in accordance with the standards.