FREDERIKSTED, VI —
OSHA Inspection: TITAN BLOCK
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of TITAN BLOCK in #8 ESTATE DIAMOND, FREDERIKSTED, VI 00840 (NAICS 327331). OSHA activity number 339390494.
Where did this inspection happen?
- Establishment
- TITAN BLOCK
- Site address
- #8 ESTATE DIAMOND
- City
- FREDERIKSTED
- State
- VI
- ZIP
- 00840
- Mailing
- #8 ESTATE DIAMOND, FREDERIKSTED, VI 00840
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 327331
- Employees
- 10
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.305 A04 V
- Issued
- Abate by
- Penalty
- Initial $1200.00 · Current $600.00 Reduced
General-duty citation text
29 CFR 1910.305(a)(4)(v): Conductors within 7 feet from the floor, thus considered exposed to physical damage, were not protected: a) On or about 08/28/13, at #8 Estate Diamond, Frederiksted, VI, in the conveyor area, the electrical conductors of the Turn Head machine were not protected from damage. b) On or about 08/28/13, at #8 Estate Diamond, Frederiksted, VI, in the cuber machine area, the electrical conductors of the machine were not protected from damage. c) On or about 08/28/13, at #8 Estate Diamond, Frederiksted, VI, in the maintenance shop area, the electrical conductors of the electrical outlet/light swtich were not protected from damage. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (2)
- — I (S) $600
- — Z (S) $1200
1910.305 B02 I
- Issued
- Abate by
- Penalty
- Initial $1200.00 · Current $600.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear: On or about 08/28/13, at #8 Estate Diamond, Frederiksted, VI, in the maintenance shop, an electrical outlet box was not covered. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (2)
- — I (S) $600
- — Z (S) $1200
1910.305 G01 IV A
- Issued
- Abate by
- Penalty
- Initial $1200.00 · Current $600.00 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure: On or about 08/28/13, at #8 Estate Diamond, Frederiksted, VI,, in the electrical room area, a flexible cord was used in lieu of permanent wiring to service a silo sensor. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (2)
- — I (S) $600
- — Z (S) $1200
1910.305 G01 IV B
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used where run through holes in walls, ceilings, or floors: On or about 08/28/13, at #8 Estate Diamond, Frederiksted, VI, in the electrical room area, a flexible cord that was connected to an electrical panel board was run through a hole on the concrete wall. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 II
- Issued
- Abate by
- Penalty
- Initial $1200.00 · Current $600.00 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(ii): Flexible cords may be used only in continuous lengths without splice or tap. Hard-service cord and junior hard-service cord No. 14 and larger may be repaired if spliced so that the splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced: On or about 08/28/13, at #8 Estate Diamond, Frederiksted, VI, in the maintenance shop area, the electrical cord of the press drill was spliced and repaired with a different electrical cord. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (2)
- — I (S) $600
- — Z (S) $1200
1910.178 L06
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.178(l)(6): The employer did not certify that each operator has been trained and evaluated as required by this paragraph (l): On or about 08/28/13, at #8 Estate Diamond, Frederiksted, VI, in the facility, where employees operate forklifts, the employee training certification had not been completed. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 327331)
SESSER, IL—2026-07-01
SESSER CONCRETE PRODUCTS COMPANY
CLARKSVILLE, TN—2026-06-30
OLDCASTLE APG SOUTH, INC.
EUGENE, OR—2026-05-28
317744337 - WILLAMETTE GRAYSTONE LLC
CHRISTIANSBURG, VA—2026-05-27
CHANEY MATERIALS, LLC
HANOVER, PA—2026-05-26
HANOVER PREST PAVING INC.
More inspections in VI
CHARLOTTE AMALIE, VI—2026-05-26
VIRGIN ISLANDS EMERGENCY MANAGEMENT AGENCY
ST CROIX, VI—2026-05-06
VI DEPARTMENT OF HEALTH
ST CROIX, VI—2026-04-28
GOV. JUAN F. LUIS HOSPITAL
ST CROIX, VI—2026-04-24
GOV. JUAN F. LUIS HOSPITAL
CHRISTIANSTED, VI—2026-04-24
OFFICE OF DISASTER RECOVERY
Source