CHICAGO, IL —
OSHA Inspection: ALSCO - AMERICAN LINEN SUPPLY CO.
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of ALSCO - AMERICAN LINEN SUPPLY CO. in 2641 S. LEAVITT STREET, CHICAGO, IL 60647 (NAICS 812331). OSHA activity number 339410466.
Where did this inspection happen?
- Establishment
- ALSCO - AMERICAN LINEN SUPPLY CO.
- Site address
- 2641 S. LEAVITT STREET
- City
- CHICAGO
- State
- IL
- ZIP
- 60647
- Mailing
- 2641 S. LEAVITT STREET, CHICAGO, IL 60647
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 812331
- Employees
- 15
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.23 C01
- Issued
- Abate by
- Penalty
- Initial $3400.00 · Current $2380.00 Reduced
General-duty citation text
29 CFR 1910.23(c)(1): Every open-sided floor or platform 4 feet or more above adjacent floor or ground level shall be guarded by a standard railing (or the equivalent as specified in paragraph (e)(3) of this section) on all open sides except where there is entrance to a ramp, stairway, or fixed ladder. The railing shall be provided with a toeboard wherever, beneath the open sides. a. Second Floor/Loading Zone - On or about September 13, 2013, linen and uniforms care workers were required to lift linen accesories (hangers, garments, and wooden pallets) to the second floor by accesing an area that was inadequately guarded with a standard guardrail. Employees were thereby exposed to fall hazards of above four (4) feet to the ground level.
Recent events (2)
- — I (S) $2380
- — Z (S) $3400
1910.23 C03
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.23(c)(3): Regardless of height, open-sided floors, walkways, platforms, or runways above or adjacent to dangerous equipment, pickling or galvanizing tanks, degreasing units, and similar hazards shall be guarded with a standard railing and toe board. a. Second Floor/Bag Lift Area - On or about September 13, 2013, the employer had an open - sided floor marked with a metal chain acrossed that was above the chute/linen's conveyor not equipped with a standard guardrail. Employees acceesing the area were potentially exposed to fall hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.23 D01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.23(d)(1): Every flight of stairs having four or more risers shall be equipped with standard stair railings or standard handrails as specified in paragraphs (d)(1)(i) through (v) of this section, the width of the stair to be measured clear of all obstructions except handrails: a. First Floor/Behind Ironer # 10 Area - On or about September 13, 2013, the employer had a "crossover" stairway with more than four (4) risers on both sides that was missing all mid railings. Employees were thereby exposed to fall hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B01 IV
- Issued
- Abate by
- Penalty
- Initial $3400.00 · Current $2380.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(1)(iv): Examination. Electric equipment shall be free from recognized hazards that are likely to cause death or serious physical harm to employees. Safety of equipment shall be determined using the following considerations: Electrical insulation a. Cleaning Laundry Areas - On or about September 13, 2013, components on electrical equipment was not closely examined on their electrical insulation conditions. Employees were thereby exposed to electrical hazards at the following locations; 1. Northside/Soil Platform - electrical insulation was pulled away from the conveyor's power switch box's cord. 2. First Floor/ # 8 Ironer Machine - electrical insulation was loose on the power supply component. 3. First Floor/by # 10 Ironer table - electrical insulation was pulled away from its fitting on the conveyor's warning light's cord.
Recent events (2)
- — I (S) $2380
- — Z (S) $3400
1910.303 B07 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment. a. Continuous Batch Washer/Chemical Pumps Area - On or about September 13, 2013, employees were required to work around electrical equipment tha was not effectively closed. Employees were potentially exposed to electrical hazards. The electrical equipment was the following; 1. The mounted outlet box for the pumps area was missing one knockout.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear. a. 2nd Floor/Garment Department/By Shirt Press Area - On or about September 13, 2013, the outlet box for the floor fan (Dayton - Model # 1YNW5A) did not have a cover/faceplate. Employees were thereby exposed to electrical hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): As a substitute for the fixed wiring of a structure; a. Garment Department/Shirt Press Area - On or about September 13, 2013, a yellow 15 feet long extension cord was being used as temporary wiring to energize a floor fan - Dayton - (Model # 1YNW5A). Employees were thereby exposed to electrical hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.1200 F01 II
- Issued
- Abate by
- Penalty
- Initial $3400.00 · Current $2380.00 Reduced
2260S227
General-duty citation text
29 CFR 1910.1200(f)(1)(ii): Labels and other forms of warning - Appropriate hazard warnings; a. Continuous Batch Washing/CBA Area - On or about September 13, 2013, the employer did not ensure that a white 100 - gallon plastic container containing a mixed solution of sodium hydroxide and sodium hypochlorite was marked with its appropriate hazard warnings. Employees were thereby exposed to the hazards associated with these chemicals. b. Waste Water Treatment Room - On or about September 13, 2013, the employer did not ensure that a white plastic container for holding a mixed solution of sodium hydroxide and sodium hypochlorite was marked with its appropriate hazard warnings. Employees were thereby exposed to the hazards associated with these chemicals.
Recent events (2)
- — I (S) $2380
- — Z (S) $3400
1910.1200 F01 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
2260S227
General-duty citation text
29 CFR 1910.1200(f)(1)(iii): labels and other forms of warning - Name and address of the chemical manufacturer, importer, or other responsible party. a. Continuous Batch Washing/CBW Area - On or about September 13, 2013, the employer did not ensure that a white 100 - gallon plastic container containing a mixed solution of sodium hydroxide and sodium hypochlorite was marked with the name and address of the chemical manufacturer, importer, or other responsible party. Employees were thereby exposed to the hazards associated with these chemicals. b. Waste Water Treatment Room - On or about September 13, 2013, the employer did not ensure that a white plastic container for holding a mixed solution of sodium hydroxide and sodium hypochlorite was marked with the name and address of the chemical manufacturer, importer, or other responsible party. Employees were thereby exposed to the hazards associated with these chemicals.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 812331)
PHOENIX, AZ—2026-06-08
CPX2026XMG193X0056 - EMERALD PHENIX LLC DBA EMERALD TEXTILE SERVICES UNDER PURESTAR COMPANY
STATELINE, NV—2026-04-22
HHS EXCEPTIONAL HOSPITALITY, LLC.
STATELINE, NV—2026-04-22
HHS EXCEPTIONAL HOSPITALITY, LLC.
ZANESVILLE, OH—2026-04-20
ECONOMY LINEN AND TOWEL SERVICE OF ZANESVILLE, INC.
CANTON, NC—2026-04-17
160990 - VESTIS SERVICES, LLC
More inspections in IL
BLOOMINGTON, IL—2026-07-13
UNKNOWN CONTRACTOR
GRANITE CITY, IL—2026-07-13
UNITED STATES STEEL CORPORATION
DECATUR, IL—2026-07-10
TILLAMOOK ILLINOIS, LLC
NEW LENOX, IL—2026-07-10
A.D GENERAL CONSTRUCTION LLC
LOCKPORT, IL—2026-07-09
ROBERTO GOMEZ DBA ROBERTO GOMEZ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339410466.