Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: DL FMS JOINT VENTURE

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of DL FMS JOINT VENTURE in 3171 N GAFFEY ST, SAN PEDRO, CA 90731 (NAICS 424710). OSHA activity number 339429896.

Watch DL FMS Joint Venture — free Get an email when a new federal OSHA severe-injury report for DL FMS Joint Venture is published. One employer, no account, unsubscribe in one click.
Site address
3171 N GAFFEY ST
City
SAN PEDRO
State
CA
ZIP
90731
Mailing
9891 BROKENLAND PARKWAY SUITE 400, COLUMBIA, MD 21046
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424710
Employees
29
Ownership type
A

9 citations on file for this inspection.

5(a)(1)

Other-than-serious 10 instances 28 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $3500.00 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees at Pier 12, the Main Terminal Tank Farm and piping systems of Defense Fuel Support Point (DFSP) in San Pedro, California where the employees were exposed to potential fire and explosion from the release of flammable liquids in that:    a)      Appropriate tools were not utilized, such as but not limited to, intrinsically safe flashlights and communications equipment where required in controlled areas.     b)      Flammable and combustible storage tanks were located less than 200 feet from the control room and adjacent industry, and were located within close proximity to an active weapons firing range.     c)      The Main Terminal control room was located less than 200 feet from a loading rack.     d)      A portable flammable storage unit was used as a testing laboratory without a hazard identification analysis and design modifications for safe human occupancy.     e)      Piping and instrumentation diagrams (P&ID) were not updated after changes and modifications to the system, such as but not limited to, the replacement of ball valves with double block and bleed valves.      f)       Management of Change (MOC) procedures were not utilized for additions, modifications or procedural changes that occurred at the facility, such as but not limited to, modification of control room monitors and valves in the piping system.     g)      Continued monitoring of the control room during loading, pump shutdowns and fuel transfers to control potential unexpected occurrences, leaks, or other emergencies was not maintained.     h)      Emergency stop buttons were not located for effective emergency response.      i)       Effective and continuous means of communication for safe operations was not available.     j)      No written safety procedures for critical operations, such as but not limited to, conducting Quality Assurance and Quality Control testing at the truck rack, Lab and at Building 103, operating the Pier 12 Loading Arms, or to address tasks that required the operator to leave the control room.
Recent events (2)
  • — I (O) $3500
  • — Z (S) $7000

1910.38 D

Deleted Serious Gravity 5 1 instance 28 exposed
Issued
Abate by
Penalty
Initial $5000.00 · Current $0.00 Reduced
29 CFR 1910.38(d):  An employer did not have and/or maintain an employee alarm system. The employee alarm system did not use a distinctive signal for each purpose that complied with the requirements in 29 CFR 1910.165:    On September 26, 2013, and at times prior thereto, the employer failed to ensure an effective emergency alert system in that radios and telephones were unreliable.
Recent events (2)
  • — I (S) $0
  • — Z (S) $5000

1910.106 B02 V A

Deleted Serious Gravity 10 1 instance 28 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $0.00 Reduced
29 CFR 1910.106(b)(2)(v)(a): Every above ground storage tank did not have some form of construction or device that will relieve excessive internal pressure caused by exposure fires:    Main Terminal, Mixing Area, Stadis 450 Tank - On September 26, 2013 and at times prior thereto, the steel atmospheric tank was not equipped with a pressure relief venting device.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7000

1910.106 C01 I

Deleted Serious Gravity 10 2 instances 28 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $0.00 Reduced
29 CFR 1910.106(c)(1)(i): The design (including selection of materials) fabrication, assembly, test, and inspection of piping systems containing flammable or combustible liquids were not suitable for the expected working pressures and structural stresses and/or did not conform with the applicable provisions of Pressure Piping, ANSI B31 series and the provisions of this paragraph:    a) Main Terminal, pumphouse building 113, pump 1 and 2:  On September 26, 2013 and at times prior thereto, the pumps were not provided with pressure relief devices against excessive pressure on the pump or on the discharge side of the pump.    b) Pier 12, JP-8 line:  On November 15, 2013 and at times prior thereto, the operating pressure was greater than the pressure design for the pipe.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7000

1910.106 C05

Deleted Serious Gravity 10 1 instance 22 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $0.00 Reduced
29 CFR 1910.106(c)(5):  All piping for flammable or combustible liquids, both above ground and underground, where subject to external corrosion, were not painted or otherwise protected.    Main terminal Valve Pit outside of Pump House Building 113:  On September 26, 2013 and at times prior thereto, above ground piping, exposed to external corrosion were not painted or had damaged insulation.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7000

1910.120 P07 I

Other-than-serious 1 instance 28 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $3500.00 Reduced
29 CFR 1910.120(p)(7)(i): Initial training for 24 hours and/or refresher training for 8 hours annually was not provided for employees:    At the establishment - On November 15, 2013 and at times prior thereto, current employees did not receive 8 hours of HAZWOPER refresher training.
Recent events (2)
  • — I (O) $3500
  • — Z (S) $7000

1910.132 A

Other-than-serious 1 instance 8 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $3500.00 Reduced
29 CFR 1910.132(a): Protective equipment was not provided when necessary whenever hazards capable of causing injury and impairment were encountered:    Main Terminal, Truck Rack:  On September 26, 2013  and at times prior thereto, personal fall protection equipment was not provided for employees working on top of tank trucks at a height of at least 8 feet where guard rails were ineffective.
Recent events (2)
  • — I (O) $3500
  • — Z (S) $7000

1910.212 A01

Other-than-serious 2 instances 6 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $3500.00 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:     Pier Terminal, Pumphouse, Pumps 2 and 3:  On November 15, 2013 and at times prior thereto, machine guarding was damaged so that employees were exposed to rotating parts.
Recent events (2)
  • — I (O) $3500
  • — Z (S) $7000

1910.305 G01 IV B

Deleted Serious Gravity 5 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $5000.00 · Current $0.00 Reduced
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors:    Pier 12, Control Room:  On November 15, 2013 and at times prior thereto, a flexible cord used to power the Pump Control Panel was run through the ceiling and subjected to damage to the insulation.
Recent events (2)
  • — I (S) $0
  • — Z (S) $5000