Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: DUFFY'S ELECTRIC, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DUFFY'S ELECTRIC, INC. in RANGELEY ROAD, ORONO, ME 04469 (NAICS 238210). OSHA activity number 339436610.

Watch Duffy'S Electric, INC. — free Get an email when a new federal OSHA severe-injury report for Duffy'S Electric, INC. is published. One employer, no account, unsubscribe in one click.
Site address
RANGELEY ROAD
City
ORONO
State
ME
ZIP
04469
Mailing
1027 MAIN ROAD, EDDINGTON, ME 04428
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

2 citations on file for this inspection.

1926.405 A02 II J

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.405(a)(2)(ii)(J): Extension cord sets used with portable electric tools and appliances shall be of three-wire type and shall be designed for hard or extra-hard usage. Flexible cords used with temporary and portable lights shall be designed for hard or extra-hard usage.   University of Maine, Planetarium - The AWM flexible cord, supplying power to the temporary lights, was not designed for hard or extra hard usage.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1926.405 G02 III

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $0.00 Reduced
29 CFR 1926.405(g)(2)(iii): Splices. Flexible cords shall be used only in continuous lengths without splice or tap. Hard service flexible cords No. 12 or larger may be repaired if spliced so that the splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced.    University of Maine, Planetarium - The No. 14 flexible cord, supplying power to the temporary lights, was not used in continuous lengths without splice or tap.
Recent events (2)
  • — I (O) $0
  • — Z (S) $2000

View DUFFY'S ELECTRIC, INC.'s full OSHA safety record →